When connecting the drive to more than one motor for simultaneous operation, disable the electronic overload protection

(L1-01 = 0) and wire each motor with its own motor thermal overload relay.
Enable motor overload protection (L1-01 = 1 to 6) when connecting the drive to a single motor, unless another motor overload

preventing device is installed. The drive electronic thermal overload function causes an oL1 fault, which shuts off the output

of the drive and prevents additional overheating of the motor. The motor temperature is continually calculated while the drive

is powered up.

n

L1-02: Motor Overload Protection Time

Setting Range: 0.1 to 5.0 min
Factory Default: 1.0 min
Parameter L1-02 determines how long the motor is allowed to operate before the oL1 fault occurs when the drive is running

a hot motor at 60 Hz and at 150% of the full load amp rating (E2-01) of the motor. Adjusting the value of L1-02 can shift the

set of oL1 curves up the y axis of the diagram below, but will not change the shape of the curves.

Operation time (minutes)

Cold start
(characteristics when an
overload occurs at a
complete stop)

Hot start
(characteristics when an
overload occurs during
continuous operation at 100%)

Motor current (%)

E2-01 = 100% motor current

10

7

3

1

0.4

0.1

0

100

150

200

Figure 59 Motor Overload Protection Time

10 Standards Compliance

YASKAWA TOEP YAIA1U 02A YASKAWA AC Drive – A1000 6-Phase/12-Pulse Input Installation Manual

89