Ul standards – Yaskawa A1000 6-Phase/12-Pulse Input User Manual

Page 84

Advertising
background image

n

EMC Filters

Install the drive with the EMC filters listed in

Table 12

to comply with the IEC/EN 61800-3 requirements.

Table 12 IEC/EN 61800-3 Filters

Drive Model

Type

Rated Current

(A)

Weight (lb)

Dimensions

[W x D x H] (in)

Y x X (in)

Qty. per Unit

Manufacturer:

Schaffner

4A0058o

FS5972-35-07

35

4.6

8.1 × 2.0 × 14.0

6.9 × 13.2

2

4A0072o

FS5972-60-07

60

8.8

9.3 × 2.6 × 16.1

8.1 × 15.4

2

4A0088o
4A0103o
4A0139o

FS5972-100-35

100

7.5

3.5 × 5.9 × 13.0

2.6 × 10.0

2

4A0165o
4A0208o

FS5972-130-35

130

10.4

3.5 × 7.1 × 14.6

2.6 × 11.6

2

4A0250o
4A0296o

FS5972-170-40

170

13.2

4.7 × 6.7 × 17.8

4.0 × 14.4

2

4A0362o

FS5972-250-37

250

25.8

5.1 × 9.5 × 24.0

3.5 × 19.6

2

4A0414o
4A0515o

FS5972-410-99

410

23.1

10.2 × 4.5 × 15.2

9.3 × 4.7

2

4A0675o

u

UL Standards

The UL/cUL mark applies to products in the United States and Canada. It indicates that UL has performed product testing and

evaluation, and determined that their stringent standards for product safety have been met. For a product to receive UL

certification, all components inside that product must also receive UL certification.

Figure 58 UL/cUL Mark

This drive is tested in accordance with UL standard UL508C and complies with UL requirements. The conditions described

below must be met to maintain compliance when using this drive in combination with other equipment:

n

Installation Area

Do not install the drive to an area greater than pollution degree 2 (UL standard).

n

Ambient Temperature

Flange Type Enclosure: -10 °C to +40 °C (14 °F to 104 °F)
Non-Flange Type Enclosure: -10 °C to +50 °C (14 °F to 122 °F)

10 Standards Compliance

84

YASKAWA TOEP YAIA1U 02A YASKAWA AC Drive – A1000 6-Phase/12-Pulse Input Installation Manual