Drive Model

Terminal

Wire Range

AWG, kcmil

Screw

Size

Tightening Torque

N·m (lb.in.)

4T0250o

R/L1, S/L2, T/L3

Refer to applicable codes for wire size

M10

18 to 23

(159.3 to 203.6)

R1/L11, S1/L21, T1/L31
U/T1, V/T2, W/T3

⊖, ⊕3

22 to 1/0 (0.3 to 53.5)

M6

2.5 to 3.0

(22.1 to 26.6)

Refer to applicable codes for wire size

M10

18 to 23

(159.3 to 203.6)

4T0296o

R/L1, S/L2, T/L3

Refer to applicable codes for wire size

M10

18 to 23

(159.3 to 203.6)

R1/L11, S1/L21, T1/L31

U/T1, V/T2, W/3

M12

32 to 40

(283.2 to 354.0)

⊖, ⊕3

22 to 1/0 (0.3 to 53.5)

M6

2.5 to 3.0

(22.1 to 26.6)

Refer to applicable codes for wire size

M12

32 to 40

(283.2 to 354.0)

4T0362o

R/L1, S/L2, T/L3

Refer to applicable codes for wire size

M10

18 to 23

(159.3 to 203.6)

R1/L11, S1/L21, T1/L31

U/T1, V/T2, W/T3

M12

32 to 40

(283.2 to 354.0)

⊖, ⊕3

22 to 1/0 (0.3 to 53.5)

M6

2.5 to 3.0

(22.1 to 26.6)

Refer to applicable codes for wire size

M12

32 to 40

(283.2 to 354.0)

4T0414o

R/L1, S/L2, T/L3

Refer to applicable codes for wire size

M12

32 to 40

(283.2 to 354.0)

R1/L11, S1/L21, T1/L31
U/T1, V/T2, W/T3

⊖, ⊕3

22 to 1/0 (0.3 to 53.5)

M6

2.5 to 3.0

(22.1 to 26.6)

Refer to applicable codes for wire size

M12

32 to 40

(283.2 to 354.0)

4T0515o

R/L1, S/L2, T/L3

Refer to applicable codes for wire size

M12

32 to 40

(283.2 to 354.0)

R1/L11, S1/L21, T1/L31
U/T1, V/T2, W/T3

⊖, ⊕3

13.3 to 127 (6 to 250)

M8

13.5 to 15

(119.5 to 132.8)

Refer to applicable codes for wire size

M12

32 to 40

(283.2 to 354.0)

4T0675o

R/L1, S/L2, T/L3

Refer to applicable codes for wire size

M12

32 to 40

(283.2 to 354.0)

R1/L11, S1/L21, T1/L31
U/T1, V/T2, W/T3

⊖, ⊕3

13.3 to 127 (6 to 250)

M8

13.5 to 15

(119.5 to 132.8)

Refer to applicable codes for wire size

M12

32 to 40

(283.2 to 354.0)

u

Wiring Checklist

No.

Item

Page(s)

Drive, Peripherals, Option Cards

1

Check drive model number to ensure receipt of correct model.

10

2

Make sure you have the correct braking resistors, DC link chokes, noise filters, and other peripheral devices.

3

Check the option card model number.

Installation Area and Physical Setup

4

Ensure that the area surrounding the drive complies with specifications.

13

Power Supply Voltage, Output Voltage

3 Electrical Installation

24

YASKAWA TOEP YAIA1U 02A YASKAWA AC Drive – A1000 6-Phase/12-Pulse Input Installation Manual

Advertising
This manual is related to the following products: