n

Low Voltage Wiring for Control Circuit Terminals

Wire low voltage wires with NEC Class 1 circuit conductors. Refer to national state or local codes for wiring. The external

power supply shall be a UL listed Class 2 power supply source or equivalent only.

Table 16 Control Circuit Terminal Power Supply

Input / Output

Terminal Signal

Power Supply Specifications

Open Collector Outputs

P1, P2, PC, DM+, DM-

Requires class 2 power supply

Digital inputs

S1 to S8, SC, HC, H1, H2

Use the internal LVLC power supply of the drive. Use class

2 for external power supply.

Analog inputs / outputs

+V, -V, A1, A2, A3, AC, AM, FM

Use the internal LVLC power supply of the drive. Use class

2 for external power supply.

n

Drive Short Circuit Rating

The drive is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical Amperes, 480 Vac

maximum (400 V Class), when protected by fuses as specified in

Factory Recommended Branch Circuit Protection

on page

85

.

u

Drive Motor Overload Protection

Set parameter E2-01 (motor rated current) to the appropriate value to enable motor overload protection. The internal motor

overload protection is UL Listed and in accordance with the NEC and CEC.

n

E2-01: Motor Rated Current

Setting Range: Model-dependent
Default Setting: Model-dependent
Parameter E2-01 protects the motor when parameter L1-01 is not set to 0. The default for L1-01 is 1, which enables protection

for standard induction motors.
If Auto-Tuning has been performed successfully, the motor data entered to T1-04 is automatically written to parameter E2-01.

If Auto-Tuning has not been performed, manually enter the correct motor rated current to parameter E2-01.

n

L1-01: Motor Overload Protection Selection

The drive has an electronic overload protection function (oL1) based on time, output current, and output frequency that protects

the motor from overheating. The electronic thermal overload function is UL-recognized, so it does not require an external

thermal relay for single motor operation.
This parameter selects the motor overload curve used according to the type of motor applied.

Table 17 Overload Protection Settings

Setting

Description

0

Disabled

Disabled the internal motor overload protection of the drive.

1

Standard fan-cooled motor (default)

Selects protection characteristics for a standard self-cooled motor with limited

cooling capabilities when running below the rated speed. The motor overload

detection level (oL1) is automatically reduced when running below the motor rated

speed.

2

Drive duty motor with a speed range of 1:10

Selects protection characteristics for a motor with self-cooling capability within a

speed range of 10:1. The motor overload detection level (oL1) is automatically

reduced when running below 1/10 of the motor rated speed.

3

Vector motor with a speed range of 1:100

Selects protection characteristics for a motor capable of cooling itself at any speed

including zero speed (externally cooled motor). The motor overload detection level

(oL1) is constant over the entire speed range.

4

Permanent Magnet motor with variable torque

Selects protection characteristics for a variable torque PM motor. The motor

overload detection level (oL1) is automatically reduced when running below the

motor rated speed.

5

Permanent Magnet motor with constant torque

Selects protection characteristics for a constant torque PM motor. The motor

overload detection level (oL1) is constant over the whole speed range.

6

Standard fan-cooled motor (50 Hz)

Selects protection characteristics for a standard self-cooled motor with limited

cooling capabilities when running below the rated speed. The motor overload

detection level (oL1) is automatically reduced when running below the motor rated

speed.

10 Standards Compliance

88

YASKAWA TOEP YAIA1U 02A YASKAWA AC Drive – A1000 6-Phase/12-Pulse Input Installation Manual