9

Parameter Table

This parameter table shows the most important parameters. Default settings are in bold type. Refer to the drive Technical

Manual for a complete list of parameters.

No.

Name

Description

A1-02

Control Method

Selection

0: V/f Control

1: V/f Control with PG

2: Open Loop Vector Control

3: Closed Loop Vector Control

5: Open Loop Vector Control for PM

6: Advanced Open Loop Vector Control for

PM

7: Closed Loop Vector Control for PM

A1-03

Initialize Parameters

0: No initialization

1110: User Initialize (parameter values

must be stored using parameter o2-03)

2220: 2-Wire initialization

3330: 3-Wire initialization

5550: oPE04 error reset

A1-06

Application Preset

0: General-purpose

1: Water supply pump

2: Conveyor

3: Exhaust fan

4: HVAC fan

5: Air compressor

b1-01

Frequency Reference

Selection 1

0: Digital operator

1: Analog input terminals

2: MEMOBUS/Modbus communications

3: Option PCB

4: Pulse train input (terminal RP)

b1-02

Run Command

Selection 1

0: Digital operator

1: Digital input terminals

2: MEMOBUS/Modbus communications

3: Option PCB

b1-03

Stopping Method

Selection

0: Ramp to stop

1: Coast to stop

2: DC Injection Braking to stop

3: Coast with timer

b1-04

Reverse Operation

Selection

0: Reverse enabled.

1: Reverse disabled.

C1-01

Acceleration Time 1

Sets the time to accelerate from 0 to

maximum frequency.

C1-02

Deceleration Time 1

Sets the time to decelerate from maximum

frequency to 0.

C2-01

S-Curve Characteristic

at Accel Start

S-curve at acceleration start.

C2-02

S-Curve Characteristic

at Accel End

S-curve at acceleration end.

C2-03

S-Curve Characteristic

at Decel Start

S-curve at deceleration start.

C2-04

S-Curve Characteristic

at Decel End

S-curve at deceleration end.

C6-01

Drive Duty Selection

0: Heavy Duty (HD)

Overload capability: 150% of drive rated

Heavy Duty current for 60 s

Default Carrier Frequency: 2 kHz

1: Normal Duty (ND)

Overload capability: 120% of drive rated

Normal Duty current for 60 s

Default Carrier Frequency: 2 kHz Swing

PWM

No.

Name

Description

C6-02

Carrier Frequency

Selection

1: 4.0 kHz

2: 6.0 kHz

3: 8.0 kHz

4: 10.0 kHz

F: User-defined (determined by C6-03 to

C6-05)

Default setting value is determined by

A1-02, Control Method Selection, C6-01,

Drive Duty Selection, and o2-04, Drive

Model Selection.

d1-01 to

d1-16

Frequency Reference 1

to 16

Sets the frequency reference for the drive.

Setting units are determined by parameter

o1-03.

d1-17

Jog Frequency

Reference

Sets the Jog frequency reference. Setting

units are determined by parameter o1-03.

d2-01

Frequency Reference

Upper Limit

Sets the frequency reference upper limit as

a percentage of the maximum output

frequency.

d2-02

Frequency Reference

Lower Limit

Sets the frequency reference lower limit as

a percentage of the maximum output

frequency.

E1-03

V/f Pattern Selection

0: 50 Hz, Constant torque 1

1: 60 Hz, Constant torque 2

2: 60 Hz, Constant torque 3 (50 Hz base)

3: 72 Hz, Constant torque 4 (60 Hz base)

4: 50 Hz, Variable torque 1

5: 50 Hz, Variable torque 2

6: 60 Hz, Variable torque 1

7: 60 Hz, Variable torque 2

8: 50 Hz, High starting torque 1

9: 50 Hz, High starting torque 2

A: 60 Hz, High starting torque 3

B: 60 Hz, High starting torque 4

C: 90 Hz (60 Hz base)

D: 120 Hz (60 Hz base)

E: 180 Hz (60 Hz base)

F: Custom V/f, E1-04 through E1-13

settings define the V/f pattern

E1-04

Maximum Output

Frequency

Parameters E1-04 and E1-06 to E1-13 can

only be changed when E1-03 is set to F.

To set linear V/f characteristics, set the

same values for E1-07 and E1-09.

In this case, the setting for E1-08 will be

disregarded. Ensure that the five

frequencies are set according to the

following rules to prevent triggering an

oPE10 fault:

E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04

Setting E1-11 to 0 disables both E1-11 and

E1-12 and the above conditions do not

apply.

Output Voltage (V)

Frequency (Hz)

E1-05
E1-12

E1-13

E1-08

E1-10

E1-09

E1-07 E1-06 E1-11 E1-04

E1-05

Maximum Voltage

E1-06

Base Frequency

E1-07

Middle Output

Frequency

E1-08

Middle Output

Frequency Voltage

E1-09

Minimum Output

Frequency

E1-10

Minimum Output

Frequency Voltage

E1-11

Middle Output

Frequency 2

E1-12

Middle Output

Frequency Voltage 2

E1-13

Base Voltage

E2-01

Motor Rated Current

Sets the motor nameplate full load current

in amps. Automatically set during

Auto-Tuning.

9 Parameter Table