8

Specifications

u

Power Ratings for Models 4T0058o to 4T0208o

Table 8 Power Ratings for Models 4T0058o to 4T0208o

Item

Specification

Drive Model

4T0058o 4T0072o 4T0088o 4T0103o

4T0139o

4T0165o 4T0208o

Maximum Applicable Motor

Capacity kW (HP)

<1>

ND Rating

30

(40)

37

(50)

45

(60)

55

(75)

75

(100)

90

(125)

110

(150)

HD Rating

22

(25-30)

30

(40)

37

(50-60)

45

(50-60)

55

(75)

75

(100)

90

(125-150)

Input

Input Current (A)

<2>

ND Rating

54

66

79

97

131

156

190

HD Rating

40

54

66

79

97

131

156

Rated Voltage

Rated Frequency

6-Phase/12-Pulse: 380 Vac to 480 Vac 50/60 Hz

Note: 6-Phase isolated supply with each of the output windings phase-shifted

by 30 electrical degrees or Hybrid 6-phase topology.

Allowable Voltage Fluctuation

-15 to 10%

Allowable Frequency Fluctuation

±5%

Input Power (kVA)

ND Rating

53.0

64.9

78.6

96.0

130

156

189

HD Rating

39.3

53.0

64.9

78.6

96.0

130

155

Output

Rated Output

Capacity (kVA)

<3>

ND Rating

<4>

44

55

67

78

106

126

159

HD Rating

34

48

57

69

85

114

137

<6>

Rated Output

Current (A)

ND Rating

<4>

58

72

88

103

139

165

208

HD Rating

45

<5>

60

<5>

75

<5>

91

<5>

112

<5>

150

<6>

180

<6>

Overload Tolerance

ND Rating: 120% of rated output current for 60 s

HD Rating: 150% of rated output current for 60 s

(Derating may be required for applications that start and stop frequently)

Carrier Frequency

User adjustable between 1 and 15 kHz

User adjustable between

1 and 10 kHz

Maximum Output Voltage (V)

Three-phase: 380 to 480 Vac (proportional to input voltage)

Maximum Output Frequency (Hz)

400 Hz (user-adjustable)

<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than

the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.

<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring conditions,

and power supply impedance. This input current rating is the 3-Phase total input current rating.

Refer to Alternative AC Drive Branch Circuit

Protection on page 85

for the 6-Phase input current rating.

<3> Rated motor capacity is calculated with a rated output voltage of 440 V.
<4> Carrier frequency is set to 2 kHz. Current derating is required in order to raise the carrier frequency.
<5> Carrier frequency can be increased to 8 kHz while keeping this current derating. Higher carrier frequency settings require derating.
<6> Carrier frequency can be increased to 5 kHz while keeping this current derating. Higher carrier frequency settings require derating.

8 Specifications

38

YASKAWA TOEP YAIA1U 02A YASKAWA AC Drive – A1000 6-Phase/12-Pulse Input Installation Manual

Advertising