Drive Specifications

Note:

1. Perform rotational Auto-Tuning to obtain the performance specifications given below.
2. For optimum performance life of the drive, install the drive in an environment that meets the required specifications.

Item

Specification

Control

Character-

istics

Control Method

The following control methods can be set using drive parameters:
• V/f Control (V/f)
• V/f Control with PG (V/f w/PG)
• Open Loop Vector Control (OLV)
• Closed Loop Vector Control (CLV)
• Open Loop Vector Control for PM (OLV/PM)
• Advanced Open Loop Vector Control for PM (AOLV/PM)
• Closed Loop Vector Control for PM (CLV/PM)

Frequency Control Range

0.01 to 400 Hz

Frequency Accuracy

(Temperature Fluctuation)

Digital input: within ±0.01% of the max output frequency (-10 to +40 °C)

Analog input: within ±0.1% of the max output frequency (25 °C ±10 °C)

Frequency Setting Resolution Digital inputs: 0.01 Hz

Analog inputs: 1/2048 of the maximum output frequency setting (11 bit plus sign)

Output Frequency Resolution 0.001 Hz

Frequency Setting Signal

Main speed frequency reference: DC -10 to +10 V (20 kΩ), DC 0 to +10 V (20 kΩ),

4 to 20 mA (250 Ω), 0 to 20 mA (250 Ω)

Main speed reference: Pulse train input (max. 32 kHz)

Starting Torque

<2>

V/f, V/f w/PG: 150% at 3 Hz
OLV: 200% at 0.3 Hz

<1>

CLV, AOLV/PM, CLV/PM: 200% at 0.0 r/min

<1>

OLV/PM: 100% at 3 Hz

Speed Control Range

<2>

V/f, V/f w/PG: 1:40

OLV: 1:200

CLV, CLV/PM: 1:1500

OLV/PM: 1:20

AOLV/PM: 1:100

Speed Control Accuracy

<2>

OLV: ±0.2% (25 °C ±10 °C)

CLV: ±0.02% (25 °C ±10 °C)

Speed Response

<2>

OLV, OLV/PM, AOLV/PM: 10 Hz (25 °C ±10 °C (77 °F ±50 °F))

CLV, CLV/PM: 50 Hz (25 °C ±10 °C (77 °F ±50 °F))

Torque Limit

Parameters setting allow separate limits in four quadrants

(available in OLV, CLV, AOLV/PM, CLV/PM)

Accel/Decel Time

0.0 to 6000.0 s (4 selectable combinations of independent acceleration and deceleration settings)

Braking Torque

Approx. 20% (approx. 125% when using braking resistor)

<3>

Short-time decel torque

<4>

: over 100% for 0.4/ 0.75 kW motors, over 50% for 1.5 kW motors, and

over 20% for 2.2 kW and above motors

<5>

(overexcitation braking/High Slip Braking: approx. 40%)

• Continuous regenerative torque: approx. 20%

<5>

(approx. 125% with dynamic braking resistor

option

<3>

: 10% ED, 10s)

V/f Characteristics

User-selected programs and V/f preset patterns possible

Main Control Functions

Torque Control, Droop Control, Speed/torque Control Switching, Feed Forward Control, Zero Servo

Function, Momentary Power Loss Ride-Thru, Speed Search, Overtorque/Undertorque Detection,

Torque Limit, 17 Step Speed (max), Accel/decel Switch, S-curve Accel/decel, 3-wire Sequence, Auto-

Tuning (rotational, stationary tuning), Dwell, Cooling Fan on/off Switch, Slip Compensation, Torque

Compensation, Frequency Jump, Upper/lower Limits for Frequency Reference, DC Injection Braking

at Start and Stop, Overexcitation Braking, High Slip Braking, PID Control (with sleep function), Energy

Saving Control, MEMOBUS/Modbus Comm. (RS-422/RS-485 max, 115.2 kbps), Fault Restart,

Application Presets, DriveWorksEZ (customized function), Removable Terminal Block with Parameter

Backup Function, Online Tuning, KEB, Overexcitation Deceleration, Inertia (ASR) Tuning,

Overvoltage Suppression, High Frequency Injection.