10 standards compliance – Yaskawa A1000 6-Phase/12-Pulse Input User Manual
Page 83
Advertising

L3
L2
L1
L3 L2 L1
L3 L2 L1
E
PE
L31
L21
L11
L3 L2 L1
L3 L2 L1
E
PE
A
D
C
A
J
K
B
F
B
E
I
G
H
A – Make sure the ground wire is
grounded
B – Grounding surface (remove any
paint or sealant)
C – Metal plate
D – Enclosure panel
E – Drive
F – Motor cable (braided shield cable,
max. 10 m)
G – Motor
H – Cable shield ground
I – Cable clamp
J – Ground plate (scrape off any
visible paint)
K – EMC noise filter
Figure 57 EMC Filter and Drive Installation for CE Compliance
10 Standards Compliance
YASKAWA TOEP YAIA1U 02A YASKAWA AC Drive – A1000 6-Phase/12-Pulse Input Installation Manual