9 parameter table – Yaskawa A1000 6-Phase/12-Pulse Input User Manual

Page 80

Advertising
background image

No.

Name

Description

L8-10

(04B6)

Heatsink Cooling Fan

Operation Selection

0: Run with timer (Fan operates only

during run and for L8-11 seconds after

stop.)

1: Run always (Cooling fan operates

whenever the drive is powered up.)

L8-11

(04B7)

Heatsink Cooling Fan

Off Delay Time

Sets a delay time to shut off the cooling fan

after the Run command is removed when

L8-10 = 0.

L8-12

(04B8)

Ambient Temperature

Setting

Enter the ambient temperature. This value

adjusts the oL2 detection level.

L8-15

(04BB)

oL2 Characteristics

Selection at Low

Speeds

0: No oL2 level reduction below 6 Hz.

1: oL2 level is reduced linearly below 6

Hz. It is halved at 0 Hz.

L8-18

(04BE)

Software Current Limit

Selection

0: Disabled

1: Enabled

L8-19

(04BF)

Frequency Reduction

Rate during Overheat

Pre-Alarm

Specifies the frequency reference reduction

gain at overheat pre-alarm when L8-03 = 4.

L8-27

(04DD)

Overcurrent Detection

Gain

Sets the gain for overcurrent detection as a

percentage of the motor rated current.

Overcurrent is detected using the lower

value between the overcurrent level of the

drive or the value set to L8-27.

L8-29

(04DF)

Current Unbalance

Detection (LF2)

0: Disabled

1: Enabled (current and voltage

detection)

2: Enabled (current detection)

3: Enabled (voltage detection)

L8-32

(04E2)

Cooling Fan Failure

Selection

Determines drive response when a fault

occurs with the internal cooling fan.

0: Ramp to stop

1: Coast to stop

2: Fast stop (Decelerate to stop using the

deceleration time set to C1-09)

3: Alarm only (“FAn” will flash)

4: Continue operation at reduced speed as

set to L8-19.

L8-35

(04EC)

Installation Method

Selection

0: IP00/Open-Chassis enclosure

1: Side-by-Side mounting

2: IP20/NEMA Type 1 enclosure

3: Finless model drive or external heatsink

installation

Set this parameter to 3 for all 6-Phase/12-

Pulse Flange and Non-Flange models.

L8-38

(04EF)

Carrier Frequency

Reduction

0: Disabled

1: Enabled below 6 Hz

2: Enabled for the entire speed range

Default setting is determined by parameters

A1-02, Control Method Selection, and

o2-04, Drive Model Selection.

No.

Name

Description

L8-40

(04F1)

Carrier Frequency

Reduction Off Delay

Time

Sets the time that the drive continues

running with reduced carrier frequency

after the carrier reduction condition is gone.

Setting 0.00 s disables the carrier frequency

reduction time.

L8-41

(04F2)

High Current Alarm

Selection

0: Disabled

1: Enabled. An alarm is triggered at output

currents above 150% of drive rated current.

L8-55

(045F)

Internal Braking

Transistor Protection

0: Disabled. Disable when using a regen

converter or optional braking unit.

1: Protection enabled.

L8-78

(02CC)

Power Unit Output

Phase Loss Protection

Enables motor protection in the event of

output phase loss.

0: Disabled

1: Enabled

L8-93

(073C)

LSo Detection Time at

Low Speed

Sets the amount of time until baseblock is

executed after detecting pull-out at low

speed.

L8-94

(073D)

LSo Detection Level at

Low Speed

Determines the detection level of pull-out

at low speed.

L8-95

(073F)

Average LSo

Frequency at Low

Speed

Sets the average number of times pull-out

can occur at low speed.

o1-03

Digital Operator

Display Selection

0: 0.01 Hz

1: 0.01% (100% = E1-04)

2: r/min (calculated using the number of

motor poles setting in E2-04, E4-04, or

E5-04)

3: User-selected units (set by o1-10 and

o1-11)

Default setting is determined by parameter

A1-02, Control Method Selection.

T1-01

Auto-Tuning Mode

Selection

0: Rotational Auto-Tuning

1: Stationary Auto-Tuning 1

2: Stationary Auto-Tuning for Line-to-Line

Resistance

3: Rotational Auto-Tuning for V/f Control

(necessary for Energy Savings and Speed

Estimation Speed Search)

4: Stationary Auto-Tuning 2

5: Stationary Auto-Tuning 3

8: Inertia Tuning (perform Rotational Auto-

Tuning prior to Inertia Tuning)

9: ASR Gain Tuning (perform Rotational

Auto-Tuning prior to ASR Gain Auto-

Tuning)

9 Parameter Table

80

YASKAWA TOEP YAIA1U 02A YASKAWA AC Drive – A1000 6-Phase/12-Pulse Input Installation Manual