Power ratings for models 4t0250 – Yaskawa A1000 6-Phase/12-Pulse Input User Manual

Page 39

Advertising
background image

u

Power Ratings for Models 4T0250o to 4T0675o

Table 9 Power Ratings for Models 4T0250o to 4T0675o

Item

Specification

Drive Model

4T0250o

4T0296o

4T0362o

4T0414o

4T0515o

4T0675o

Maximum Applicable Motor

Capacity kW (HP)

<1>

ND Rating

132

(200)

160

(250)

185

(300)

220

(350)

250

(400)

355

(500-550)

HD Rating

110

(150)

132

(200)

160

(250)

185

(300)

220

(350)

315

(400-450-500)

Input

Input Current (A)

<2>

ND Rating

228

275

317

376

427

603

HD Rating

190

228

275

317

376

511

Rated Voltage

Rated Frequency

6-Phase/12-Pulse: 380 Vac to 480 Vac 50/60 Hz

Note: 6-Phase isolated supply with each of the output windings phase-shifted

by 30 electrical degrees or Hybrid 6-phase topology.

Allowable Voltage Fluctuation

-15 to 10%

Allowable Frequency Fluctuation

±5%

Input Power (kVA)

ND Rating

227

274

316

375

425

601

HD Rating

189

227

275

316

375

534

Output

Rated Output

Capacity (kVA)

<3>

ND Rating

<4>

191

226

276

316

392

514

HD Rating

165

<5>

198

<5>

232

<5>

282

<4>

343

<4>

461

<4>

Rated Output

Current (A)

ND Rating

<4>

250

296

362

414

515

675

HD Rating

216

<5>

260

<5>

304

<5>

370

<4>

450

<4>

605

<4>

Overload Tolerance

ND Rating: 120% of rated output current for 60 s

HD Rating: 150% of rated output current for 60 s

(Derating may be required for applications that start and stop frequently)

Carrier Frequency

User adjustable between 1 and 10 kHz

User adjustable between 1 and 5 kHz

Maximum Output Voltage (V)

Three-phase: 380 to 480 Vac (proportional to input voltage)

Maximum Output Frequency (Hz)

400 Hz (user-adjustable)

<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than

the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.

<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring conditions,

and power supply impedance. This input current rating is the 3-Phase total input current rating.

Refer to Alternative AC Drive Branch Circuit

Protection on page 85

for the 6-Phase input current rating.

<3> Rated motor capacity is calculated with a rated output voltage of 440 V.
<4> Carrier frequency is set to 2 kHz. Current derating is required in order to raise the carrier frequency.
<5> Carrier frequency can be increased to 5 kHz while keeping this current derating. Higher carrier frequency settings require derating.

8 Specifications

YASKAWA TOEP YAIA1U 02A YASKAWA AC Drive – A1000 6-Phase/12-Pulse Input Installation Manual

39

Advertising
This manual is related to the following products: