9 parameter table – Yaskawa A1000 6-Phase/12-Pulse Input User Manual

Page 79

Advertising
background image

No.

Name

Description

H5-07

RTS Control Selection

0: Disabled. RTS is always on.

1: Enabled. RTS turns on only when

sending.

H5-09

Communication Fault

Detection Time

Sets the time required to detect a

communications error.

H5-10

Unit Selection for

MEMOBUS/Modbus

Register 0025H

0: 0.1 V units

1: 1 V units

H5-11

Communications

ENTER Function

Selection

0: Drive requires an Enter command

before accepting any changes to

parameter settings.

1: Parameter changes are activated

immediately without the Enter command.

H5-12

Run Command

Method Selection

0: FWD/Stop, REV/Stop

1: Run/Stop, FWD/REV

H6-01

Pulse Train Input

Terminal RP Function

Selection

0: Frequency reference

1: PID feedback value

2: PID setpoint value

3: V/f Control with Simple PG feedback

(possible only when using motor 1 in V/f

Control)

H6-02

Pulse Train Input

Scaling

Sets the terminal RP input signal frequency

that is equal to 100% of the value selected

in H6-01.

H6-03

Pulse Train Input Gain

Sets the level of the value selected in H6-01

when a frequency with the value set in

H6-02 is input.

H6-04

Pulse Train Input Bias Sets the level of the value selected in H6-01

when 0 Hz is input.

H6-05

Pulse Train Input Filter

Time

Sets the pulse train input filter time

constant.

H6-06

Pulse Train Monitor

Selection

Select the pulse train monitor output

function (value of the o-oo part of

Uo-oo).

For example, enter “501” for U5-01.

H6-07

Pulse Train Monitor

Scaling

Sets the terminal MP output signal

frequency when the monitor value is 100%.

For example, to have the pulse train monitor

output equal the output frequency, set

H6-06 to 102 and H6-07 to 0.

H6-08

Pulse Train Input

Minimum Frequency

Sets the minimum frequency for the pulse

train input to be detected. Enabled when

H6-01 = 0, 1, or 2.

L1-01

Motor Overload

Protection Selection

0: Disabled

1: General purpose motor (standard fan

cooled)

2: Drive dedicated motor with a speed range

of 1:10

3: Vector motor with a speed range of 1:100

4: PM motor with variable torque

5: PM motor with constant torque control

6: General purpose motor (50 Hz)

Default setting is determined by parameter

A1-02, Control Method Selection.

L1-02

Motor Overload

Protection Time

Sets the motor thermal overload protection

(oL1) time.

L2-01

Momentary Power

Loss Operation

Selection

0: Disabled. Drive trips on Uv1 fault

when power is lost.

1: Recover within the time set in L2-02. Uv1

will be detected if power loss is longer than

L2-02.

2: Recover as long as CPU has power. Uv1

is not detected.

3: KEB deceleration for the time set to

L2-02.

4: KEB deceleration as long as CPU has

power.

5: KEB deceleration to stop.

No.

Name

Description

L3-04

Stall Prevention

Selection during

Deceleration

0: Disabled. Deceleration at the active

deceleration rate. An ov fault may occur.

1: General purpose. Deceleration is

paused when the DC bus voltage exceeds

the Stall Prevention level.

2: Intelligent. Decelerate as fast as possible

while avoiding ov faults.

3: Stall Prevention with braking resistor.

Stall Prevention during deceleration is

enabled in coordination with dynamic

braking.

4: Overexcitation Deceleration.

Decelerates while increasing the motor

flux.

5: Overexcitation Deceleration 2. Adjust

the deceleration rate according to the DC

voltage.

L5-01

Number of Auto

Restart Attempts

Sets the number of times the drive may

attempt to restart after the following faults

occur: GF, LF, oC, oH1, oL1, oL3, oL4, ov,

Sto, Uv1.

L6-01

Torque Detection

Selection 1

0: Disabled

1: oL3 detection only active during speed

agree, operation continues after detection

2: oL3 detection always active during run,

operation continues after detection

3: oL3 detection only active during speed

agree, output shuts down on an oL3 fault

4: oL3 detection always active during run,

output shuts down on an oL3 fault

5: UL3 detection only active during speed

agree, operation continues after detection

6: UL3 detection always active during run,

operation continues after detection

7: UL3 detection only active during speed

agree, output shuts down on a UL3 fault

8: UL3 detection always active during run,

output shuts down on a UL3 fault

L6-02

Torque Detection

Level 1

Sets the overtorque and undertorque

detection level.

L6-03

Torque Detection Time

1

Sets the time an overtorque or undertorque

condition must exist to trigger torque

detection 1.

L8-01

Internal Dynamic

Braking Resistor

Protection Selection

(ERF type)

0: Resistor overheat protection disabled

1: Resistor overheat protection enabled

L8-02

Overheat Alarm

Level

An overheat alarm occurs when heatsink

temperature exceeds the L8-02 level.

L8-03

(04AF)

Overheat Pre-Alarm

Operation Selection

0: Ramp to stop. A fault is triggered.

1: Coast to stop. A fault is triggered.

2: Fast Stop. Decelerate to stop using the

deceleration time in C1-09. A fault is

triggered.

3: Continue operation. An alarm is

triggered.

4: Continue operation at reduced speed as

set in L8-19.

L8-05

(04B1)

Input Phase Loss

Protection Selection

Selects the detection of input current phase

loss, power supply voltage imbalance, or

main circuit electrolytic capacitor

deterioration.

0: Disabled

1: Enabled

L8-07

(04B3)

Output Phase Loss

Protection Selection

0: Disabled

1: Enabled (triggered by a single phase

loss)

2: Enabled (triggered when two phases are

lost)

L8-09

(04B5)

Output Ground Fault

Detection Selection

0: Disabled

1: Enabled

Default setting is determined by parameters

C6-01, Drive Duty Selection, and o2-04,

Drive Model Selection.

9 Parameter Table

YASKAWA TOEP YAIA1U 02A YASKAWA AC Drive – A1000 6-Phase/12-Pulse Input Installation Manual

79

Advertising
This manual is related to the following products: