Wiring terminal functions and voltages – Yaskawa V7N Drive with DeviceNet User Manual

Page 11

Advertising
background image

TERMINAL

FUNCTION

VOLTAGE / SIGNAL LEVEL

L1 (R)

230V Drive: 200 / 208 / 220 / 230V at 50/60 Hz

L2 (S)

Main circuit input power supply

460V Drive: 380 / 400 / 440 / 460 / 480V

L3 (T)

at 50/60 Hz

T1 (U)
T2 (V)

Main circuit output

230V Drive: 0 - 200 / 208 / 220 / 230V

T3 (W)

460V Drive: 0 - 400 / 440 / 460 / 480V

B1

For connection of braking resistor (option)

B2

+1

DC Reactor terminals

+2

DC Bus terminals (+1 & –)

Ground terminal (100 ohms or less)

– – – –

S1

Multi-Function-Input 1

Factory setting is "

Forward Run/Stop

" (1).

(Forward run when closed, stop when open)

S2

Multi-Function-Input 2

Factory setting is "

Reverse Run/Stop

" (1).

(Reverse Run when closed, stop when open)

S3

Multi-Function-Input 3

Factory setting is "

External Fault (NO contact)

input

" (1)

S4

Multi-Function-Input 4

Factory setting is "

Fault Reset

" (1)

SC

Sequence common for terminals S1-S4.

Common terminal for sequence inputs

P1

Multi-Function Open

Factory setting is

Collector Output 1

"

Drive Running

"

Photocoupler output:

P2

Multi-Function Open

Factory setting is

48 VDC; 50 mA or less.

Collector Output 2

"

Speed Agree

"

PC

Multi-Function Open

0 V

Collector Output common

CN2 V

Frequency reference voltage input

0 to +10 / 100% (20K )

CN2 I

Frequency reference current input

4 to 20 mA (250 )

CN2 C

Frequency reference input common

0V

Section 4

Tightening

Wire

Model

Terminal Symbol

Screw

Torque

Applicable size

Recommended

lb • in (N • m)

size

Type

mm

2

AWG

mm

2

AWG

1.94 to 2.21

twisted wire 0.5 to 0.75 20 to 18

Shielded

S1 to S4, P1, P2, SC, PC

M2

(0.22 to 0.25) single

0.5 to 1.25 20 to 16

0.75

18

wire or

equivalent

4.44 to 5.33

Thin

DeviceNet

DeviceNet Connector

M3

(0.5 to 0.6)

twisted wire 0.2 to 2.5

24 to 12

0.32/.2 22/24

Cable

Table 1-1. Wire and Terminal Screw Sizes - continued

Common

to

all models

Table 1-2. Terminal Functions and Voltages

NOTES:

1.

These inputs have factory settings based on 2-wire reset. For 3-wire reset definitions, see Figure 1-6.

TERMINAL

NAME

FUNCTION

BLACK

V-

DeviceNet power supply ground

BLUE

CAN_L

DeviceNet data low

GREEN

Shield

Shield wire

WHITE

CAN_H

DeviceNet data high

RED

V+

DeviceNet power supply +24VDC

Table 1-3. Terminal Functions and Signals of DeviceNet

11

Wiring

Terminal Functions and Voltages

IG.V7N.qxd:IG.V7N.qxd 6/5/07 3:22 AM Page 11