In order to conform to EMC standards, the following methods are required for line filter application,
cable shielding and Drive installation.

The line filter and Drive must be mounted on the same metal plate. The filter should be mounted as
close to the Drive as practical. The cable must be kept as short as possible and the metal plate
should be securely grounded. The ground of the line filter and the Drive must be bonded to the
metal plate with as much bare-metal contact as possible.

For main circuit input cables, a screened cable is recommended within the panel and is also
suggested for external connections. The screen of the cable should be connected to a solid ground.
For the motor cables, a screened cable (max. 20 m) must be used and the screen of the motor
cable should be connected to ground at both ends by a short connection, again using as much bare-
metal contact as practical.

For a more detailed explanation, refer to the manufacturer document EZZ006543, “Installation
Guidelines For EMC Directive using AC Drive Products.”

Table 1-4 and Figure 1-4 show the line filter list for EMC standards and the installation/wiring of the
Drive and line filter.

Table 1-4. Line Filters for EMC Standards

Model

Line Filter

CIMR-V7NU

Part Number

Rated

Weight

Dimensions in in. (mm)

Mounting Dim. in in. (mm)

Screw

FIL00

Current (A)

lbs. (kg)

H x W x D

(1)

H1 x W1

Size

20P1
20P2
20P4

1083

10

1.8 (0.8)

7.6 x 3.2 x 2.0 (194 x 82 x 50)

7.1 x 2.4 (181 x 62)

M5

20P7
21P5

1084

16

2.2 (1.0) 6.7 x 4.4 x 2.0 (169 x 111 x 50)

6.1 x 3.6 (156 x 91)

M5

22P2
23P7

1085

26

2.4 (1.1) 6.9 x 5.7 x 2.0 (174 x 144 x 50) 6.3 x 4.7 (161 x 120)

M5

25P5

1100

50

5.1 (2.3) 12.0 x 7.2 x 2.2 (304 x 184 x 56) 11.3 x 5.9 (288 x 150)

M6

27P5
40P2

1086

5

2.2 (1.0) 6.7 x 4.4 x 1.8 (169 x 111 x 45)

6.1 x 3.6 (156 x 91)

M5

40P4
40P7

1087

10

2.2 (1.0) 6.7 x 4.4 x 1.8 (169 x 111 x 45)

6.1 x 3.6 (156 x 91)

M5

41P5
42P2
43P7

1088

15

2.4 (1.1) 6.9 x 5.7 x 2.0 (174 x 144 x 50) 6.3 x 4.7 (161 x 120)

M5

45P5
47P5

1101

30

5.1 (2.3) 12.0 x 7.2 x 2.2 (304 x 184 x 56) 11.3 x 5.9 (288 x 150)

M6

(1)

D is the distance the filter will extend outward from the surface of the metal plate.

Motor Cable

max. 20m

Cable Length

max. 40cm

L2

PE

L1

L3

MAINS

LOAD

FILTER

V7N

DRIVE

L2

L1

L3

L1

L3

L2

Ground Bands (remove any paint)

Ground Bands (remove any paint)

Metal Plate

IM
3~

W1

W

H1

H

D

4-d

Figure 1-4. Installation of Line Filter and V7N Drive