Section 5

18

Supported Assemblies
DeviceNet

Yaskawa Supported Input Instances

Instance

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Function Code ( Only MODBUS functions register read (03h) and register write (10h) are supported)

1

2

Register Number

3

100 (64h)

MODBUS

Message

4

Data

Note:

Refer to output assembly instance 150 (96h) for response

Instance

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Terminal S7

Terminal S6

Terminal S5

Terminal S4

Terminal S3

Run REV

Run FWD

1

Terminal P2

Terminal P1

Terminal MA

Fault

Reset

External

Fault

2

3

Speed Reference (Scaled by Parameter n035)

4

5

Reserved

6

101 (65h)
Standard

Control

7

Reserved

Note

*

Terminals S5, S6, S7 and MA are only available through DeviceNet

Instance

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Terminal S7

Terminal S6

Terminal S5

Terminal S4

Terminal S3

Run REV

Run FWD

1

Terminal P2

Terminal P1

Terminal

MA

Fault Reset

External Fault

2

3

Speed Reference (Scaled by Parameter n035)

4

5

Acc Time 1

6

102(66h)

Acc/Dec Time

Control

7

Dec Time 1

Note

*

Terminals S5, S6, S7 and MA are only available through DeviceNet

Instance

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Terminal S7

Terminal S6

Terminal S5

Terminal S4

Terminal S3

Run REV

Run FWD

1

Terminal P2

Terminal P1

Terminal MA

Function Code 2

Function Code 1

Fault Reset

External Fault

2

3

Speed Reference (Scaled by Parameter n035)

4

5

Register Address

6

0105(69h)

Standard

DI/DO Control

7

Register Data

Code 1 Code 2

Description

0 0

Invalid

0 1

Write Modbus Data

1 0

Read Modbus Data

Func Code

1 1

Invalid

Refer to output assembly instance 155 (9Bh) for response

Note

*

Terminals S5, S6, S7 and MA are only available through DeviceNet

Instance

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Terminal S7

Terminal S6

Terminal S5

Terminal S4

Terminal S3

Run REV

Run FWD

1

Terminal P2

Terminal P1

Terminal MA

Fault

Reset

External

Fault

2

3

Speed Reference (Scaled by Parameter n035)

4

5

Reserved

6

106 (6Ah)

Standard

Control

7

Reserved

Note

*

Terminals S5, S6, S7 and MA are only available through DeviceNet

IG.V7N.qxd:IG.V7N.qxd 6/5/07 3:22 AM Page 18