Drive parameters – Yaskawa V7N Drive with DeviceNet User Manual

Page 26

Advertising
background image

26

The Drive control circuits use various parameters to select functions and characteristics of the Drive.
Changing of parameter settings must be done in the Program mode, or by use of the Function
LEDs, if available (see TM.V7N.01, Section 4).

Drive Parameters

PARA-

ADDR

CLASS 100

NAME

DATA

SETTING RANGE

SETTING

FACTORY

METER

INST. 01

(AND UNITS)

INCREMENT SETTING

0

0: n001 can be read and set;

n002 - n179 read only

1

1: n001 - n039 can be read and set

2

2: n001 - n079 can be read and set

3

3: n001 - n119 can be read and set

n001 101h

01h

Parameter Selection /

4

4: n001 - n179 can be read and set

Initialization

5

5: n001 - n179 can be read and set

1

1

RUN command accepted during Program mode

6

6: Clear Fault History Only

7

7: Not Used

8

8: 2-wire Initialization (Japan Spec.)

9

9: 3-wire Initialization (Japan Spec.)

10

10:2 wire initialization (USA Spec)

11

11:3 wire initialization (USA Spec.)

n002 102h

02h

Control Method Selection

0

0: V/f Control

1

0

1

1: Open Loop Vector

0

0: Digital Operator

n003 103h

03h

Operation Method Selection

1

1: Terminal

1

3

2

2: Not Used

3

3: DeviceNet

0

0: Digital Operator Pot

1

1: Frequency Reference 1 (n024)

2

2: Not Used

3

3: Not Used

n004 104h

04h

Reference Selection

4

4: Not Used

5

5: Not Used

1

9

6

6: Not Used

7

7: Multi-Function Analog Input (0 to 10V) (CN2)

8

8: Multi-Function Analog Input (4 to 20 mA) (CN2)

9

9: DeviceNet

n005 105h

05h

Stop Method

0

0: Ramp to stop

1

0

1

1: Coast to stop

n006 106h

06h

Reverse Prohibit

0

0: Reverse Run enabled

1

0

1

1: Reverse Run disabled

0

0: STOP key is effective regardless of

programming of n003

n007 107h

07h

STOP Key Function

1

1: STOP key is effective only when sequence

1

0

command (per n003) is from Digital Operator

0

0: Frequency Reference from digital

n008 108h

08h

Reference Selection -

operator pot

1

0

Digital Operator

1

1: Frequency Reference from n024

0

0: ENTER key must be pressed to write-in

n009 109h

09h

Frequency Reference Setting

new value

1

0

Method From Digital Operator

1

1: ENTER key does not have to be pressed

to write-in new value

Operation Selection

0

0: Disabled (operation continues)

n010 10Ah

0Ah

When Digital Operator is

1

1: Enabled (motor coasts to a stop and fault

1

0

Disconnected

is displayed)

n011 10Bh

0Bh

Frequency - Max.

-

50.0 to 400.0

0.1 (Hz)

60.0

n012 10Ch

0Ch

Voltage - Max.

-

0.1 to 255.0 (230V Drive)

0.1 (V)

230.0

0.2 to 510.0 (460V Drive)

460.0

n013 10Dh

0Dh

Frequency - Max.

-

0.2 to 400.0

0.1 (Hz)

60.0

Voltage Point

n014 10Eh

0Eh

Frequency - Midpoint

-

0.1 to 399.9

0.1 (Hz)

(Note 2)

n015 10Fh

0Fh

Voltage - Midpoint

-

0.1 to 255.0 (230V Drive)

0.1 (V)

(Note 2)

0.2 to 510.0 (460V Drive)

n016 110h

10h

Frequency - Min.

-

0.1 to 10.0

0.1 (Hz)

(Note 2)

n017 111h

11h

Voltage - Min.

-

0.1 to 50.0 (230V Drive)

0.1 (V)

(Note 2)

0.2 to 100.0 (460V Drive)

Section 9

Drive Parameter Listing
(n001-n017)

IG.V7N.qxd:IG.V7N.qxd 6/5/07 3:22 AM Page 26