Drive parameters - continued – Yaskawa V7N Drive with DeviceNet User Manual

Page 31

Advertising
background image

31

PARA- ADDR CLASS 100

NAME

DATA

SETTING RANGE

SETTING

FACTORY

METER

INST. 01

(AND UNITS)

INCREMENT SETTING

0

0:

PID control disabled

1

1:

D = Feed Forward

2

2:

D = Feedback

3

3:

Reference + PID (D = Feed Forward)

4

4:

Reference + PID (D = Feedback)

n128 180h

D3h

PID Control Selection

5

5:

Inverse PID - D = Feed Forward

1

0

6

6:

Inverse PID - D = Feedback

7

7:

Inverse PID - Reference + PID
(D = Feed Forward)

8

8:

Inverse PID - Reference + PID
(D = Feedback)

n129 181h

D4h

PID Feedback Gain (Note 4)

-

0.00 to 10.00

0.01

1.00

n130 182h

82h

PID Proportional Gain (Note 4)

-

0.00 to 25.00

0.1

1.0

n131 183h

83h

PID Integral Time (Note 4)

-

0.00 to 360.00

0.1 s

1.0

n132 184h

84h

PID Derivative Time (Note 4)

-

0.00 to 2.50

0.01

0.00

n133 185h

85h

PID Offset Adjustment (Note 4)

-

-100 to 100

1%

0

n134 186h

86h

Integral Value Limit (Note 4)

-

-100 to 100

1%

100

n135 187h

87h

PID Output Lag Filter Time

(Note 4)

-

0.0 to 10.0

0.1 s

0.0

Feedback Loss

0

0:

Disabled

n136 188h

88h

Detection Selection

1

1:

Enabled - Alarm (operation continues)

1

0

2

2:

Enabled Fault (coast to stop)

n137 189h

89h

Feedback Loss Detection Level

-

0 to 100

1%

0

n138 18Ah

8Ah

Feedback Loss Detection Time

-

0.0 to 25.5

0.1 s

1.0

0:

Energy saving disabled

n139 18Bh

8Bh

Energy Saving Selection

0

1:

Energy saving enabled

1

0

(Note 5)

1

Note: Energy saving becomes enabled by

(Energy Saving)

V/f control mode

n140 18Ch

8Ch

Energy Saving Gain

-

0.00 to 6550

0.1 or 1

(Note 1)

K2 (Energy Saving)

n141 18Dh

8Dh

Energy Saving Voltage Lower

-

0 to 120

1%

50

Limit at 60 Hz (Energy Saving)

n142 18Eh

8Eh

Energy Saving Voltage Lower

-

0 to 25

1%

12

Limit at 6 Hz (Energy Saving)

n143 18Fh

8Fh

Time of Average kW

-

1 to 200

1

1

(Energy Saving)

(x 24 ms)

(24 ms)

n144 190h

90h

Voltage Limit of Tuning

-

1 to 100

1%

0

(Energy Saving)
Step Voltage of Tuning to

n145 191h

91h

100% Output Voltage

-

0.1 to 10.0

0.1%

0.5

(Energy Saving)
Step Voltage of Tuning to

n146 192h

92h

5% Output Voltage

-

0.1 to 10.0

0.1%

0.2

(Energy Saving)

46h 70: Basic Speed Control Output Instance
47h 71: Extended Speed Control Output Instance
96h 150: V7N Modbus I/O Control Output Instance

70, 71,

97h 151: V7N Standard Drive Control Output

150, 151,

n148 194h

94h

DeviceNet I/O Polled

Instance

152, 155,

71

Producing Attribute

98h 152: V7N Accel/Decel Time Control Output

156

Instance

9Bh 155: Expanded I/O Modbus Output Instance
9Ch 156: V7N General Purpose DI/DO Output Instance

14h 20: Basic Speed Control Input Instance
15h 21: Extended Speed Control Input Instance
64h 100: V7N Modbus I/O Control Input

Instance

20, 21,

n149 195h

95h

DeviceNet I/O Polled

65h 101: V7N Standard Drive Control Input

100, 101,

21

Consuming Attribute

Instance

102, 105,

66h 102: V7N Accel/Decel Time Control Input

106

Instance

69h 105: Expanded I/O Modbus Input Instance

6Ah 106: V7N General Purpose DI/DO Input Instance

n150 196h

96h

DeviceNet MAC ID

-

0 to 63

1

0

0

0: Coast to stop

1

1: Decel to stop using Decel Time 1 (n020)

n151 197h

97h

DeviceNet Timeover Detection

2

2: Decel to stop using Decel Time 2 (n022)

1

0

Selection

3

3: Operation continues with Alarm

4

4: Disabled

0

0: 125 kbps

n152 198h

98h

DeviceNet Baud Rate

1

1: 250 kbps

1

2

Selection

2

2: 500 kbps

3

3: Auto Baud

n153 199h

99h

DeviceNet Speed Scale

-

-15 to 15

1

0

n154 19Ah

9Ah

DeviceNet Current Scale

-

-15 to 15

1

0

n155 19Bh

9Bh

DeviceNet Electric Power

-

-15 to 15

1

0

Scale

n156 19Ch

9Ch

DeviceNet Voltage Scale

-

-15 to 15

1

0

n157 19Dh

9Dh

DeviceNet Time Scale

-

-15 to 15

1

0

Drive Parameters - Continued

Section 9

Drive Parameter Listing

(n128-n157)

IG.V7N.qxd:IG.V7N.qxd 6/5/07 3:22 AM Page 31