19

Supported Assemblies

DeviceNet

Yaskawa Supported Output Instances

Instance

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Function Code*

1

2

Register Number

3

150(96h)

MODBUS

Message

4

Data

Refer to Input Instance 100 (64Refer to Input Instance 100 (64h)

Note:

*

A Modbus message error is returned if the function code has the MSB (bit 80h) set

Instance

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

@Fault @Alarm @Ready

@

Speed

Agree

@Fault Reset

@REV Run

@ Zero Speed

@FWD Run

1

@Terminal P2 @Terminal P1 @Terminal MA @Local Mode

@ UV

@OPE

2

3

Output Frequency (Scaled by Parameter n035)

4

5

Reserved

6

151(97h)

Standard

Control

7

Output Current (0.01A or 0.1A Based on Drive Capacity)

Note

*

Terminal MA is only available through DeviceNet

/Instance

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

@Fault

@Alarm

@Ready

@ Speed Agree

@Fault Reset

@REV Run

@ Zero Speed

@FWD Run

1

@Terminal P2

@Terminal P1 @Terminal MA @Local Mode

@ UV

@OPE

2

3

Output Frequency (Scaled by Parameter n035)

4

5

Speed Reference (Scaled by Parameter n035)

6

152(98h)

Enhanced

Control/

MODBUS

Message

7

Output Current

Note

*

Terminal MA is only available through DeviceNet

Instance

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

@Fault

@Alarm

@Ready

@ Speed Agree

@Fault Reset

@REV Run

@ Zero Speed

@FWD Run

1

@Terminal P2 @Terminal P1 @Terminal MA @Local Mode

Function Bit 2

Function Bit 1

@UV

@OPE

2

3

Speed Actual (Scaled by Parameter n035)

4

5

Register Address

6

155(9Bh)

Standard DI/DO

Control

7

Register Data

Code 1 Code 2

Description

0 0

Invalid

0 1

During Modbus Command Execution

1 0

Error

Func Code

1 1

Execution Complete

Refer to input assembly instance 105 (69h)

Note

*

Terminal MA is only available through DeviceNet

Instance

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

@Fault

@Alarm

@Ready

@ Speed Agree

@Fault Reset

@REV Run

@ Zero Speed

@FWD Run

1

@Terminal P2

@Terminal P1 @Terminal MA @Local Mode

@ UV

@OPE

2

3

Speed Actual Frequency (Scaled by Parameter n035)

4

5

Reserved

6

156(9Ch)

Standard DI/DO

Control

7

Output Current

Note

*