Drive parameters - continued – Yaskawa V7N Drive with DeviceNet User Manual

Page 30

Advertising
background image

30

PARA- ADDR CLASS 100

NAME

DATA

SETTING RANGE

SETTING

FACTORY

METER

INST. 01

(AND UNITS)

INCREMENT SETTING

0

0:

Detection Disabled

1

1:

Detect only at set frequency;
operation continues

2

2:

Detect only at set frequency;

n096 160h

60h

Overtorque Detection (OL3)

coast to stop

1

0

3

3:

Detect during all frequency conditions;
operation continues

4

4:

Detect during all frequency conditions;
coast to stop

Overtorque Detection

n097 161h

61h

Selection (OL3)

0

0:

Detected by output torque

1

0

(Note 5)

1

1:

Detected by output current

n098 162h

62h

Overtorque Detection
Level (OL3)

-

30 to 200

1 (%)

160

n099 163h

63h

Overtorque Detection
Delay Time (OL3)

-

0.1 to 10.0

0.1 (sec)

0.1

n100 164h

64h

Up/Down Hold

0

0:

Disabled

Memory

1

1:

Enabled

1

0

n101 165h

65h

Speed Search
Deceleration Time

-

0.0 to 10.0

0.1 (sec)

2

n102 166h

66h

Speed Search Operation

-

Level

0 to 200%

1 (%)

150

n103 167h

67h

Torque Compensation Gain

-

0.0 to 2.5

0.1

1.0

(Note 4)

n104 168h

68h

Torque Compensation

-

Time Constant

0.0 to 25.5

0.1 (sec)

(Note 2)

n105 169h

69h

Torque Compensation

-

0.1 (W) or

Iron Loss

0.0 to 6550

1 (W)

(Note 1)

n106 16Ah

6Ah

Motor Rated Slip (Note 4)

-

0.0 to 20.0

0.1 (Hz)

(Note 1)

n107 16Bh

6Bh

Motor Line-to-line

-

0.001 (ohm)

Resistance

0.000 to 65.50

(Note 1)

n108 16Ch

6Ch

Motor Leakage

-

0.01 (mH)

Inductance (Note 1)

0.00 to 655.0

or 0.1 (mH)

(Note 1)

n109 16Dh

6Dh

Torque Compensation

-

1 (%)

Limit (Note 1)

0 to 250

150

n110 16Eh

6Eh

Motor No-load Current

-

0 to 99

1 (%)

(Note 1)

n111 16Fh

6Fh

Slip Compensation Gain (Note 4)

-

0.0 to 2.5

0.1

(Note 2)

n112 170h

70h

Slip Compensation Primary

-

0.0 to 25.5

0.1 (sec)

(Note 2)

Delay Time

n113 171h

71h

Slip Compensation Selection

0

0:

Disabled

1

0

During Regeneration (Note 1)

1

1:

Enabled

0

0:

Disabled

n115 173h

73h

Stall Prevention Above Base

(level is based on setting of n094)

Speed During Run

1

1:

Enabled

1

0

(level at Fmax is n094 x 0.4)

0

0:

Follows acc/dec #1 (n019, n020)
or acc/dec #2 (n021, n022)

n116 174h

74h

Stall Prevention During Run,

Note: Multi-Function input selectable

1

0

Accel/Decel Time Select

1

1:

Follows acc/dec #2 (n021, n022)
always

0

0:

Undertorque detection disabled

1

1:

Detected during constant speed running.
Operation continues after detection

Undertorque Detection

2

2:

Detected during constant speed running.

n117 175h

75h

Select (UL3)

Operation stops during detection

1

0

3

3:

Detected during all frequency conditions.
Operation continues

4

4:

Detected during all frequency conditions.
coast to stop

0 to 200%

n118 176h

76h

Undertorque Detection

-

Inverter rated current = 100%; if n097 = 0

1(%)

10

Level (detection by torque);

motor rated torque
becomes 100%

n119 177h

77h

Undertorque Detection

-

0.1 (sec)

Time

0.1 to 10.0

0.1

n120 178h

78h

Frequency Reference 9 (Note 4)

n121 179h

79h

Frequency Reference 10 (Note 4)

0.01 (Hz)

n122 17Ah

7Ah

Frequency Reference 11 (Note 4)

(< 100 Hz)

n123 17Bh

7Bh

Frequency Reference 12 (Note 4)

-

0.00 to 400.00

or

0.00

n124 17Ch

7Ch

Frequency Reference 13 (Note 4)

0.1 (Hz)

n125 17Dh

7Dh

Frequency Reference 14 (Note 4)

(>= 100 Hz)

n126 17Eh

7Eh

Frequency Reference 15 (Note 4)

n127 17Fh

7Fh

Frequency Reference 16 (Note 4)

Drive Parameters - Continued

Section 9

Drive Parameter Listing
(n096-n127)

IG.V7N.qxd:IG.V7N.qxd 6/5/07 3:22 AM Page 30