PARA- ADDR CLASS 100

NAME

DATA

SETTING RANGE

SETTING

FACTORY

METER

INST. 01

(AND UNITS)

INCREMENT SETTING

n158 19Eh

9Eh

Motor Code (Energy Saving)

-

0 to 70

1

Note 1

Energy Saving Voltage

n159 19Fh

9Fh

Upper Limit At 60 Hz

-

0 to 120

1%

120

(Energy Saving)

Energy Saving Voltage

n160 1A0h

A0h

Upper Limit At 6 Hz

-

0 to 25

1%

16

(Energy Saving)

n161 1A1h

A1h

Power Supply Detection

-

0 to 100

1%

10

Hold Width (Energy Saving)

n162 1A2h

A2h

Power Supply Detection

-

0 to 255

1

5

Filter Time Constant

(x 4 ms)

(20 ms)

n163 1A3h

A3h

PID Output Gain

-

0.0 to 25.0

0.1

1.0

0

0: Not Used

1

1: Not Used

2

2: Not

Used

n164 1A4h

A4h

PID Feedback Selection

3

3: Multi-Function Analog Input

1

0

(Voltage 0 - 10V) (CN2)

4

4: Multi-Function Analog Input

(Current 4 - 20mA) (CN2)

5

5: Not Used

n166 1A6h

A6h

Input Phase Loss

-

0 to 100 (%)

1%

0

Detection Level

n167 1A7h

A7h

Input Phase Loss

-

0 to 255 (sec)

1 sec

0

Detection Time

n168 1A8h

A8h

Output Phase Loss

-

0 to 100 (%)

1%

0

Detection Level

n169 1A9h

A9h

Output Phase Loss

-

0.0 to 2.0 (sec)

0.1 sec

0

Detection Time

0

0: 0.1 Hz

1AAh

AAh

Modbus Frequency

1

1: 0.01 Hz

n170

Unit Selection

2

2: 30,000/100%

1

0

3

3: 0.1%

n173 1ADh

ADh

DC Injection P Gain

-

1 to 999

1 (0.001) 83 (0.083)

n174 1AEh

AEh

DC Injection I Time

-

1 to 250

1 (4ms)

25

(100ms)

Reduce Carrier

0

0: Disabled

n175 1B0h

B0h

at low speed selection

1

1: Carrier Frequency reduced to 2.5kHz

1

0

when Fout <= 5Hz & Iout >= 110%

Rdy

rdy: READY status

rdy

rEd

rEd: READ executes

rEd

n176

Digital Operator Parameter

CPy Cpy: COPY executes

Cpy

rdy

1B1h

B1h

Copy Function Selection

vFy

vFy: VERIFY executes

vFy

vA

vA:

Inverter capacity display

vA

Sno

Sno: Software No. display

Sno

Digital Operator

0

0: Read prohibited

n177 1B2h

B2h

Parameter copy

1

1: Read allowed

1

0

Access Selection

n178 1B3h

B3h

Fault History

-

(Note 3)

N/A

N/A

n179 1B4h

B4h

Software Number

-

(Note 3)

N/A

N/A

(Note 6)

Drive Parameters - Continued

Note 1: Factory setting differs depending on V7N capacity.
Note 2: Factory setting differs depending on control method selected (n002).
Note 3: n178 and n179 are display only parameters
Note 4: Parameter can be changed while V7N is operating.
Note 5: Available only in CIMR-V7NU25P5, 27P5, 45P5, and 47P5 Drives.
Note 6: Software number should be 3005 or higher for ADR functionality

Section 9

Drive Parameter Listing
(n158-n179)