Drive parameters - continued – Yaskawa V7N Drive with DeviceNet User Manual

Page 29

Advertising
background image

29

PARA- ADDR CLASS 100

NAME

DATA

SETTING RANGE

SETTING

FACTORY

METER

INST. 01

(AND UNITS)

INCREMENT SETTING

Analog Frequency Reference

n070 146h

46h

Filter Time Constant

-

0.00 to 2.00

0.01 s

0.10

(CN2, Voltage Ref Input)

n071 147h

47h

Analog Frequency Reference

-

-255 to 255

1%

100

Gain (CN2, Current Ref Input)

n072 148h

48h

Analog Frequency Reference

-

-100 to 100

1%

0

Bias (CN2, Current Ref Input)

Analog Frequency Reference

n073 149h

49h

Filter Time Constant

-

0.00 to 2.00

0.01 s

0.10

(CN2, Current Ref Input)

0

0: Multi-Function analog input disabled

1

1: Aux. Frequency reference

n077 14Dh

4Dh

Multi-Function Analog

2

2: Frequency gain

1

0

Input CN2 Selection

3

3: Frequency bias

4

4: Voltage bias

n078 14Eh

4Eh

Multi-Function Analog Input

0

0: 0 - 10V

1

0

Signal Selection

1

1: 4 - 20 mA

n079 14Fh

4Fh

Multi-Function Digital Input

0

0: Scans twice with 8 msec scan rate

1

0

Scan Rate Selection

1

1: Scans twice with 2 msec scan rate

n080 150h

50h

Carrier Frequency

-

1 to 4 (x 2.5 kHz)

1

3

7 to 9 (synchronous)

0

0: Not Provided

1

1: Continuous operation after power

n081 151h

51h

Momentary Power Loss

recovery within 2 sec.

1

0

Ride-through Method

2

2: Continuous operation after power

recovery within control logic time
(no fault output)

n082 152h

52h

Number of auto restarts

-

0 to 10

1

0

attempts

n083 153h

53h

Prohibit Frequency 1

-

0.00 to 400.0

0.01 (Hz)

0.00

or 0.1 (Hz)

n084 154h

54h

Prohibit Frequency 2

-

0.00 to 400.0

0.01 (Hz)

0.00

or 0.1 (Hz)

n085 155h

55h

Prohibit Frequency 3

-

0.00 to 400.0

0.01 (Hz)

0.00

or 0.1 (Hz)

n086 156h

56h

Prohibit Frequency Deadband

-

0.00 to 25.50

0.01 (Hz)

0.00

n087 157h

57h

Elapsed Time Function

0

0: Time elapses when power is On

0

Selection

(5)

1

1: Time elapses when Drive is running

n088 158h

58h

Elapsed Operation Time

-

0 to 9999 hours

0

(Initial Value)

(5)

n089 159h

59h

DC Injection Current

-

0 to 100

1 (%)

50

n090 15Ah

5Ah

DC Injection Time at stop

-

0.0 to 25.5

0.1 (sec)

0.0

n091 15Bh

5Bh

DC Injection Time at start

-

0.0 to 25.5

0.1 (sec)

0.0

n092 15Ch

5Ch

Stall Prevention During

0

0: Enabled

1

0

Deceleration

1

1: Disabled

n093 15Dh

5Dh

Stall Prevention During

-

30 to 200

1 (%)

170

Acceleration

n094 15Eh

5Eh

Stall Prevention Level During

-

30 to 200

1 (%)

160

Running

n095 15Fh

5Fh

Frequency Detection Level

-

0.00 to 400.0

0.01 (Hz)

0.00

or 0.1 (Hz)