Yaskawa Portable Control Display Unit User Manual
Page 68
 
Forcing (FRC) Menu
01/22/96
7
FORCING MENU
62
•
Pressing the ESC key will exit the 
Forcing mode without altering 
anything that has not been changed 
up to this point. The PCDU will 
return to the screen showing 
the initial value for the selected PAC 
block: 
(NUMI PAC BLOCK)
(LOGO PAC BLOCK)
OR
Note: When the ESC key is pressed
repeatedly in any menu, the PCDU 
will back up all the way to the top 
greeting message. The FRC menu 
is an exception to this rule. This is 
done to minimize the possibility 
of the operator leaving the I/O in 
the forcing mode without knowing 
it. If the ESC key is pressed 
repeatedly and there is at least one 
I/O currently being force, the PCDU 
will display the following screen:
This is how the PCDU informs the 
operator that there is at least one 
PAC block in the forcing state. It is 
assumed that the operator has read 
the “Forcing active....” message and 
therefore is aware of this fact after 
the F3 key is pressed.
Forcing active
(Press F3 key)
LOGO Block 00444
OFF
NUMI Block 00200
55.