Internally, the X-Pedition 8600 DC power supply consists of two separate power supplies. Each of
these internal power supplies must be energized to produce sufficient power for the
X-Pedition 8600 to operate. Each internal power supply is connected to source power through a
pair of positive (+) and negative (-) wiring lugs on the wiring block.

Figure 27

shows the internal

relationship of the wiring lugs of the X-Pedition 8600 DC power supply.

Figure 27. Relationship of wiring lugs on X-Pedition 8600 DC power supply

Note:

For the X-Pedition 8600 to work properly, both positive (+) terminals and both negative (-)
terminals of the X-Pedition 8600 DC power supply MUST be connected to the DC source.

Because of the X-Pedition 8600 DC supply current requirements, each pole of the 48 Volt DC
source should use 6 gauge wire. Each 6 gauge wire can be divided into two 12 gauge wires by using
a conductive splitter-block. This creates two 12 gauge wires carrying positive (+) current and two
12 gauge wires carrying negative current. In turn, both 12 gauge positive (+) wires and both 12

Internal Power Supply One

Internal Power Supply Two

XP-8600 DC Power Supply

These lugs supply power
to Power Supply One

These lugs supply power
to Power Supply Two