ProSoft Technology MVI69-DFNT User Manual

Page 100

Advertising
background image

Reference

MVI69-DFNT ♦ CompactLogix or MicroLogix Platform

User Manual

EtherNet/IP Client/Server Communication Module

Page 100 of 167

ProSoft Technology, Inc.

May 14, 2014

The DFNT module supports server functionality using the reserved ControlNet
service port 0xAF12. Services supported in the module permit client applications
(that is, RSView, ControlLogix processors, and RSLinx) to read from and write to
the module’s database. This section discusses the requirements for attaching to
the module using several client applications.
The following illustration shows the relationship of the DFNT module’s
functionality to devices on an Ethernet network:

Client

Server

RSSql

RSLinx

ControlLogix

Processor

PLC5

Processor

SLC5/05

Processor

DDE/OP C

Apps

RSView

SoftLogix

DFNT MODULE

DB

Server functionality places all data transfer operations outside the module. There
is no configuration required in the module other than setting up the network and
database parameters in the configuration file. Ladder logic in attached
processors use MSG instructions to perform read and write operations on the
module’s internal database. When RSLinx links a user application to the module,
the module’s server functionality must be used. RSLinx exists on an Ethernet
network only as a client application. It cannot act as a server. User applications
can use the DDE/OPC capabilities built into RSLinx to interface with the data in
the DFNT module. RSView can link directly to the module using drivers supplied
by RSLinx.