background image

Ladder Logic

MVI69-DFNT ♦ CompactLogix or MicroLogix Platform

User Manual

EtherNet/IP Client/Server Communication Module

Page 56 of 167

ProSoft Technology, Inc.

May 14, 2014

4 Enter the values shown in the following illustration to define the module

correctly for the MicroLogix processor, and then click OK

to save your

configuration.

The Input Words and Output Words parameters will depend on the Block
Transfer Size
parameter you specify in the configuration file. Use the values
from the following table.

Block Transfer Size

Input Words

Output Words

60

62

61

120

122

121

240

242

241

5 Click OK

to continue.

6 After completing the module setup, the I/O Configuration dialog box will

display the module's presence.

The last step is to add the ladder logic. If you are using the example ladder logic,
adjust the ladder to fit your application.

Download the new application to the controller. If you encounter errors when you
attempt to run the program, refer to Diagnostics and Troubleshooting (page 57)
for information on how to connect to the module's Config/Debug port to use its
troubleshooting features.