Configuring the MVI69-DFNT Module

MVI69-DFNT ♦ CompactLogix or MicroLogix Platform

User Manual

EtherNet/IP Client/Server Communication Module

Page 30 of 167

ProSoft Technology, Inc.

May 14, 2014

2.2

[Module]

This section describes how to initialize the module upon startup.

2.2.1 Failure Flag Count

0 through 65535

This parameter specifies the number of successive transfer errors that must
occur before halting communication on the application port(s). If the parameter is
set to 0, the application port(s) will continue to operate under all conditions. If the
value is set larger than 0 (1 to 65535), communications will cease if the specified
number of failures occur.

2.2.2 Initializing Output Data

Y

ES

or N

O

This parameter determines if the output data for the module should be initialized
with values from the processor. If the value is set to N

O

(0), the output data will

be initialized to 0. If the value is set to Y

ES

(1), the data will be initialized with

data from the processor. Setting this option to Y

ES

requires associated ladder

logic to pass the data from the processor to the module.