ProSoft Technology MVI69-DFNT User Manual

Page 49

Advertising
background image

MVI69-DFNT ♦ CompactLogix or MicroLogix Platform

Ladder Logic

EtherNet/IP Client/Server Communication Module

User Manual

ProSoft Technology, Inc.

Page 49 of 167

May 14, 2014

7 The imported rung will contain the Add-On instruction with two CPS

instructions as follows below. The CPS instructions are set by default for a
length of 62/61 words.

Edit the above CPS instructions Length field values according to the following
table.

"Block Transfer Size"
Parameter
(60/120/240 options)

Ladder Routine window:

Connection Parameters: CPS instructions Length field values:

Block

Transfer

Size

Input

Size

Output

Size

60

62

61

62

61

120

122

121

122

121

240

242

241

242

241