MVI69-DFNT ♦ CompactLogix or MicroLogix Platform
Ladder Logic
EtherNet/IP Client/Server Communication Module
User Manual
ProSoft Technology, Inc.
Page 49 of 167
May 14, 2014
7 The imported rung will contain the Add-On instruction with two CPS
instructions as follows below. The CPS instructions are set by default for a
length of 62/61 words.
Edit the above CPS instructions Length field values according to the following
table.
"Block Transfer Size"
Parameter
(60/120/240 options)
Ladder Routine window:
Connection Parameters: CPS instructions Length field values:
Block
Transfer
Size
Input
Size
Output
Size
60
62
61
62
61
120
122
121
122
121
240
242
241
242
241