Reference

MVI69-DFNT ♦ CompactLogix or MicroLogix Platform

User Manual

EtherNet/IP Client/Server Communication Module

Page 134 of 167

ProSoft Technology, Inc.

May 14, 2014

5.4

Cable Connections

The MVI69-DFNT module has the following functional communication
connections installed:
 One Ethernet port (RJ45 connector)
 One RS-232 Configuration/Debug port (RJ45 connector)

5.4.1 Ethernet Connection

The MVI69-DFNT module has an RJ45 port located on the front of the module,
labeled Ethernet, for use with the TCP/IP network. The module is connected to
the Ethernet network using an Ethernet cable between the module’s Ethernet
port and an Ethernet switch or hub.

Note: Depending on hardware configuration, you may see more than one RJ45 port on the
module. The Ethernet port is labeled Ethernet.

Warning: The MVI69-DFNT module is NOT compatible with Power Over Ethernet (IEEE802.3af /

IEEE802.3at) networks. Do NOT connect the module to Ethernet devices, hubs, switches or

networks that supply AC or DC power over the Ethernet cable. Failure to observe this precaution
may result in damage to hardware, or injury to personnel.

Important: The module requires a static (fixed) IP address that is not shared with any other device

on the Ethernet network. Obtain a list of suitable IP addresses from your network administrator

BEFORE configuring the Ethernet port on this module.