ProSoft Technology MVI69-DFNT User Manual

Page 61

Advertising
background image

MVI69-DFNT ♦ CompactLogix or MicroLogix Platform

Diagnostics and Troubleshooting

EtherNet/IP Client/Server Communication Module

User Manual

ProSoft Technology, Inc.

Page 61 of 167

May 14, 2014

Module Errors

Problem Description

Steps to take

BP ACT LED remains
OFF or blinks slowly

This indicates that backplane transfer operations are failing. Connect to the
module’s Configuration/Debug port to check this.
To establish backplane communications, verify the following items:

The processor is in RUN mode

The backplane driver is loaded in the module

The module is configured for read and write block data transfer

The ladder logic handles all read and write block situations

The module is configured in the processor

OK LED remains RED

The program has halted or a critical error has occurred. Connect to the
Configuration/Debug port to see if the module is running. If the program has
halted, turn off power to the rack, remove the card from the rack and re-
insert the card in the rack, and then restore power to the rack.