MVI69-DFNT ♦ CompactLogix or MicroLogix Platform

Reference

EtherNet/IP Client/Server Communication Module

User Manual

ProSoft Technology, Inc.

Page 85 of 167

May 14, 2014

During normal program operation, the module sequentially sends read blocks
and requests write blocks. For example, if the application uses three read and
two write blocks, the sequence will be as follows:

R0W1

R1W2

R2W1

R3W2

R0W1

R1W2

R2W1

R3W2

Notice that ReadBlock 0, the read block that contains status information, appears
at the start of each read block cycle. This means status information in the
controller tags will update only after all other read data blocks have been
updated.

The sequence will continue unless interrupted by special function write block
numbers sent by the controller or by a command request from a node on the
DFNT network or operator control through the module’s Configuration/Debug
port. For more information, see Special Function Blocks.

Here are some additional examples of alternative backplane communication
setups.

Assume that the backplane parameters are configured as follows:

Read Register Start: 0
Read Register Count: 480
Write Register Start: 480
Write Register Count: 480

The module data areas would be allocated as follows:

Database address 0 to 479 will be continuously transferred from the module to
the processor. Database address 480 to 959 will be continuously transferred
from the processor to the module.