Ladder Logic

MVI69-DFNT ♦ CompactLogix or MicroLogix Platform

User Manual

EtherNet/IP Client/Server Communication Module

Page 52 of 167

ProSoft Technology, Inc.

May 14, 2014

2 Select the 1769-Module (Generic 1769 Module) from the list and click OK.

3 Enter the Name, Description and Slot options for your application, using the

values in the illustration above. You must select the Comm Format as D

ATA

-

INT in the dialog box, otherwise the module will not communicate over the
backplane of the CompactLogix rack.

4 Configure the Connection Parameters to match to the Block Transfer Size

parameter in the configuration file. Use the values in the table corresponding
with the block transfer size you configured.

Block Transfer Size = 60

Field

Recommended Value

Type

1769-MODULE Generic 1769 Module

Parent

Local

Name

MVI69

Description

MVI69 Application Module

Comm Format

Data - INT

Slot

The slot number in the rack where the module is installed

Input Assembly Instance

101

Input Size

62

Output Assembly Instance

100

Output Size

61

Configuration Assembly Instance

102

Configuration Size

0