Diagnostics and Troubleshooting

MVI69-DFNT ♦ CompactLogix or MicroLogix Platform

User Manual

EtherNet/IP Client/Server Communication Module

Page 68 of 167

ProSoft Technology, Inc.

May 14, 2014

Resetting Diagnostic Data

Press [U]

to reset the status counters for the Client and/or server(s) in the

module.

Viewing Version Information

Press [V]

to view version information for the module.

Use this command to view the current version of the software for the module, as
well as other important values. You may be asked to provide this information
when calling for technical support on the product.

Values at the bottom of the display are important in determining module
operation. The Program Scan Counter value is incremented each time a
module’s program cycle is complete.

Tip: Repeat this command at one-second intervals to determine the frequency of program
execution.

Warm Booting the Module

Press [W]

from the Main menu to warm boot (restart) the module.

This command will cause the program to exit and reload, refreshing configuration
parameters that must be set on program initialization. Only use this command if
you must force the module to reboot.