ProSoft Technology MVI69-DFNT User Manual

Page 75

Advertising
background image

MVI69-DFNT ♦ CompactLogix or MicroLogix Platform

Diagnostics and Troubleshooting

EtherNet/IP Client/Server Communication Module

User Manual

ProSoft Technology, Inc.

Page 75 of 167

May 14, 2014

4.2.7 Network Menu

From the Main menu press [@]

to display the Network menu. The Network menu

allows you to send, receive, and view the WATTCP.CFG file that contains the IP
and module addresses, and other network information.

Transferring WATTCP.CFG to the Module

Press [R]

to transfer a new WATTCP.CFG file from the PC to the module. Use

this command to change the network configuration for the module (for example,
the module’s IP address).
Press [Y]

to confirm the file transfer, and then follow the instructions on the

terminal screen to complete the file transfer process.

Transferring WATTCP.CFG to the PC

Press [S]

to transfer the WATTCP.CFG file from the module to your PC.

Press [Y]

to confirm the file transfer, and then follow the instructions on the

terminal screen to complete the file transfer process.

After the file has been successfully transferred, you can open and edit the file to
change the module’s network configuration.

Viewing the WATTCP.CFG File on the module

Press [V]

to view the module’s WATTCP.CFG file. Use this command to confirm

the module’s current network settings.

Returning to the Main Menu

Press [M]

to return to the Main menu.

Advertising