Reference

MVI69-DFNT ♦ CompactLogix or MicroLogix Platform

User Manual

EtherNet/IP Client/Server Communication Module

Page 106 of 167

ProSoft Technology, Inc.

May 14, 2014

Client Command List
In order for the client to function, the module's Client Command List must be
defined. This list contains up to 100 individual entries, with each entry containing
the information required to construct a valid command. This includes the
following:
 Command enable mode ((0) disabled, (1) continuous or (2) conditional)
 IP address of the remote server
 Slot number for processor when interfacing with a ControlLogix processor
 Command Type - Read or Write command
 Database Address - Determines where data will be placed and/or obtained
 Address information to access data in remote unit
 Count - Select the number of words to be transferred
 Poll Delay - (1/10