ProSoft Technology MVI69-DFNT User Manual

Page 156

Advertising
background image

Reference

MVI69-DFNT ♦ CompactLogix or MicroLogix Platform

User Manual

EtherNet/IP Client/Server Communication Module

Page 156 of 167

ProSoft Technology, Inc.

May 14, 2014

5.8.12 Function Code #501 - Protected Typed Logical Read (Two

Address Fields)

Column

Parameter

Description

Parameter

1

Enable/Type Word

0=Disabled and 1=Continuous.

2

Virtual Database Address

This parameter defines the database address of the first

data point to be associated with the command.

3

Poll Interval

Minimum number of seconds to wait before polling with
this command.

4

Count

Number of data word values to be considered by the
function.

5

Swap Type Code

Swap type code for command: 0=None, 1=Swap words,

2=Swap words & bytes and 3=swap bytes in each word.

6

Node Address

Address of unit to reach on the data highway.

7

Slot Number

Processor slot number in Control/CompactLogix rack.

Use -1 for PLC5 & SLC processors.

8

Function Code = 501

Logical Read Command

9

File Type

SLC file type letter as used in file name string. Valid
values for the system are N, S, F, A, ….

P1

10

File Number

SLC file number to be associated with the command.

P2

11

Element Number

The parameter defines the element in the file where
write operation will start.

P3

12

Not Used

This field is not used by the command. Values entered

in this column will be ignored.

P4

This function reads one or more words of data from a PLC data table.

Advertising
This manual is related to the following products: