2.2.3 DFNT Server File Size

100 or 1000

Sets the maximum file size (100 or 1000) for the servers. Servers emulate
PCCC-type data table addressing. Use 100

to simulate SLC-type data tables,

which are size-limited to 256 elements per table. Use 1000 to simulate PLC-type
data tables, which are size-limited to 1000 elements per table. For use with
ControlLogix or CompactLogix systems, either size may be used.

2.2.4 Read Register Start

0 to 3999

This parameter specifies the starting register address of a block of data registers
to transfer from the module to the processor. This will be used for data brought
into the processor from other nodes on the network.

2.2.5 Read Register Count

0 to 3960

This parameter specifies the number of registers to be transferred from the
module to the processor. This will be used for data brought into the processor
from other nodes on the network.

2.2.6 Write Register Start

0 to 3999

This parameter specifies the starting register address of a module register block
where data transferred from the processor will be stored. This will be used for
data to be sent from the processor to other nodes on the network.

2.2.7 Write Register Count

0 to 3960

This parameter specifies the number of registers to transfer from the processor to
the module. This will be used for data to be sent from the processor to other
nodes on the network.

2.2.8 Block Transfer Size

60, 120 or 240

This read-only parameter specifies the number of words of user data transferred
in each block between the module and processor.