Ladder Logic

MVI69-DFNT ♦ CompactLogix or MicroLogix Platform

User Manual

EtherNet/IP Client/Server Communication Module

Page 54 of 167

ProSoft Technology, Inc.

May 14, 2014

5 Click N

EXT

to continue.

6 Select the Requested Packet Interval value for scanning the I/O on the

module. This value represents the minimum frequency at which the module
will handle scheduled events. It should not be set to less than 1 millisecond.
Values between 5 and 10 milliseconds should work with most applications.

7 S

AVE

the module. Click OK to dismiss the dialog box. The Controller

Organization window now displays the module's presence. The following
illustration shows the Controller Organization window:

8 Copy the User-defined Data Types (UDTs) from the sample program.
9 Copy the Controller Tags from the sample program.
10 Copy the Ladder Rungs from the sample program.
11 Save and download the new application to the controller.