5 When the internal countdown register decrements to zero (0), the Slave

Status register for that slave will be set to a value of one (1), which will allow

a command to be sent in an attempt to re-establish communication with the

slave.

The Slave Disable and Slave Enable Special Control Blocks can be used to

access the Slave Status table and control slave polling through ladder logic by

forcing values into the Slave Status table in a manner similar to how the module's

internal firmware operates automatically.
Using the Disable control will force a value of three (3) into the internal module

register that holds the Slave Status information for that port and slave address. In

this situation, when a Slave Status register is set to three (3), the slave at the

corresponding address will not be polled, even if there are commands in the

Command List that are enabled and addressed to that slave. Since the E

RROR

D

ELAY

C

OUNTER

is not involved in this operation, the status register will remain

set to 3, disabling the slave, until it is re-enabled with the Enable control.
Using the Enable control will force a value of one (1) into the table. When a Slave

Status register is set to one (1), the slave at the corresponding address will be

polled as specified in the Command List.
Here are the Special Control Block codes for performing these functions.

Block ID

Description

3000

Disable list of slaves on Port 1

3001

Enable list of slaves on Port1

3100

Disable list of slaves on Port 2

3101

Enable list of slaves on Port 2

Port 1 slaves can be disabled using block code 3000 and can be enabled using

block code 3001. Port 2 slaves can be disabled using block code 3100 and can

be enabled using block code 3101. Each output (Write) block can contain a list

of up to 59 slave addresses to disable or enable.

Write Block - Disable Slaves
Here is structure of the Disable Slaves output image block.

Offset

Description

Length (words)

0

3000 or 3100

1

1

Number of slaves to disable with this block

1

2 to 60

List of addresses of the slaves to disable

59

61 to ( n )

Spare (present only if Block Transfer Size > 60)

( n - 60 )

( n ) = 120 or 240 (if configured)
The module will respond with an input image block with the same identification

code and indicate the number of slaves disabled by this function.