4.3
Reading Status Data from the Module
The MVI69-MCM module returns a 29-word Status Data block that can be used
to determine the module’s operating status. This data is located in the module’s
database at registers 6670 to 6698 and at the location specified in the
configuration. This data is transferred to the CompactLogix or MicroLogix
processor continuously.