Configuring the MVI69-MCM Module

MVI69-MCM ♦ CompactLogix or MicroLogix Platform

User Manual

Modbus Communication Module

Page 52 of 167

ProSoft Technology, Inc.

March 22, 2011

Write Register Count
0 to 5000
The Write Register Count parameter specifies the size of the Write Data area of

module memory and the number of registers to transfer from the processor to

this memory area, up to a maximum value of 5000 words.

Note: Total Read Register Count and Write Register Count cannot exceed 5000 total registers.
Read Data and Write Data Areas must be configured to occupy separate address ranges in
module memory and should not be allowed to overlap.

Backplane Fail Count
0 to 65535
This parameter specifies the number of consecutive backplane transfer failures

that can occur before communications should be halted.

Error/Status Block Pointer
-1 to 4939
Starting register location in virtual Modbus database for the error/status table. If a

value of -1 is entered, the error/status data will not be placed in the database. All

other valid values determine the starting location of the data. This data area

includes the module version information and all server error/status data. Refer to

Status Data Definition for more information.

Initializing Output Data
Y

ES

or N

O

This parameter determines if the output data for the module should be initialized

with values from the processor. If the value is set to N

O

(0), the output data will

be initialized to 0. If the value is set to Y

ES

(1), the data will be initialized with

data from the processor. Use of this option requires associated ladder logic to

pass the data from the processor to the module.

Block Transfer Size
60, 120 or 240
This read-only parameter specifies the number of words in each block transferred

between the module and processor.