MVI69-MCM ♦ CompactLogix or MicroLogix Platform

Configuring the MVI69-MCM Module

Modbus Communication Module

User Manual

ProSoft Technology, Inc.

Page 63 of 167

March 22, 2011

(Modbus Command parameters)
DB Addr - Tells the Master where in its data memory is the beginning of data to

obtain and write out to the Slave (slave) device.
Reg Count - Tells the Master how many data points to send to the Slave. Two

counts will mean two floating points with Float Flag: Y and the "Addr in Dev" =>

the "Float Start" Parameter.
Swap Code - Tells the Master how to orient the Byte and Word structure of the

data value. This is device dependent. Check Command Entry formats Section.
Func Code - Tells the Master to write the float values to the Slave. FC16.
Addr in Dev - Tells the Master where in the Slave's database to locate the data.
In the above example, the Master's Modbus command to transmit inside the

Modbus packet will be as follows.

Slave
address

Function
Code

Address in
Device

Reg count

Byte Count

Data

DEC

01

16

7100

2

8

85.37 22.86

HEX

01

10

1B BC

00 02

08

BD 71 42 AA E1 48 41 B6

In this example, the Master's Modbus packet contains the data byte and data

word counts that have been doubled from the amount specified by Reg Count

due to the Float flag set to Y. Some Slaves look for the byte count in the data

packet to know the length of the data to read from the wire. Other slaves know at

which byte the data begins and read from the wire the remaining bytes in the

packet as the data the Master is sending.

Specific Example#2: Master is issuing Modbus command with FC 16 (with Float Flag: No) to
transfer Float data.