ProSoft Technology MVI69-MCM User Manual

Page 65

Advertising
background image

MVI69-MCM ♦ CompactLogix or MicroLogix Platform

Configuring the MVI69-MCM Module

Modbus Communication Module

User Manual

ProSoft Technology, Inc.

Page 65 of 167

March 22, 2011

Func Code - Tells the Master to read the register values from the Slave. FC3.
Addr in Dev - Tells the Master where in the Slave's database to obtain the data.
In the above example, the Master's Modbus command to transmit inside the

Modbus packet will be as follows.

Slave address

Function Code

Address in Device

Reg count

DEC

01

3

6100

2

HEX

01

03

17 D4

00 02

In the above example the (Enron/Daniel supporting) Slave's Modbus command to

transmit inside the Modbus packet will be as follows.

Slave address

Function Code

Byte Count

Data

DEC

01

3

8

32.75 275.69

HEX

01

03

08

00 00 42 03 D8 52 43 89

In the above example the (a NON-Enron/Daniel supporting) Slave's Modbus

command that will be transmitted inside the Modbus packet will be as follows.

Slave address

Function Code

Byte Count

Data

DEC

01

3

4

32.75

HEX

01

03

04

00 00 42 03

Enable
0 to 4
This field defines whether the command is to be executed and under what

conditions.
If the parameter is set to 0, the command is disabled and will not be executed in

the normal polling sequence.
Setting the parameter to a value of 1 for the command causes the command to

be executed each scan of the command list if the Poll Interval Time is set to zero.

If the Poll Interval time is set, the command will be executed, when the interval

timer expires.
If the parameter is set to 2, the command will execute only if the internal data

associated with the command changes. This value is valid only for write

commands.
A value of 3 can be used to enable a write command continuously (similar to

enable code of 1), but if the float flag and float start parameters are being used,

the module will only send out a standard 16 bit write. Only valid for FC 6, and 16

when the MB Address in Device >= Float Start Parameter and Float Flag is set to

Yes.
A value of 4 will provide the same disabling of floating point writes as the enable

code of 3, but utilizing conditional writes (similar to enable code 2 functionality).

Important: Not all revisions of the MCM driver support this parameter. To determine if your module
supports this parameter, contact ProSoft Technical Support.

Advertising