ProSoft Technology MVI69-MCM User Manual
Page 32
Configuring the MVI69-MCM Module
MVI69-MCM ♦ CompactLogix or MicroLogix Platform
User Manual
Modbus Communication Module
Page 32 of 167
ProSoft Technology, Inc.
March 22, 2011
1 In the
I/O
C
ONFIGURATION
folder, click the right mouse button to open a
shortcut menu, and then choose New Module.
2 Select 1769-MODULE
3 Fill the module properties as follows:
Parameter
Value
Name
Enter a module identification string. Example:
MVI69MCM_2
Description
Enter a description for the module. Example: ProSoft
communication module for Serial Modbus communications.
Comm Format
Select Data-INT
Slot
Enter the slot number in the rack where the MV69-MCM
module will be installed.
Input Assembly Instance
101
Input Size
62 / 122 / 242
Output Assembly Instance
100
Output Size
61 / 121 / 241
Configuration Assembly Instance
102
Configuration Size
0