ProSoft Technology MVI69-MCM User Manual

Page 138

Advertising
background image

Reference

MVI69-MCM ♦ CompactLogix or MicroLogix Platform

User Manual

Modbus Communication Module

Page 138 of 167

ProSoft Technology, Inc.

March 22, 2011

Response
The addressed Slave responds with its address and the function code followed

by the information field. The information field contains 1 byte describing the

quantity of data bytes to be returned. The contents of the registers requested

(DATA) are 2 bytes each, with the binary content right justified within each pair of

characters. The first byte includes the high order bits and the second, the low

order bits.
Because the Slave interface is normally serviced at the end of the controller's

scan, the data will reflect the register content at the end of the scan. Each PC will

limit the quantity of register contents provided each scan; thus for large register

quantities, multiple PC scans will be required, and the data provided will be form

sequential scans.
In the example below the register 3009 contains the decimal value 0.

Adr

Func

Byte Count

Data Input Reg Hi

Data Input Reg Lo

Error Check Field

11

04

02

00

00

E9

5.6.6 Force Single Coil (Function Code 05)

Query
This message forces a single coil either ON or OFF. Any coil that exists within

the controller can be forced to either state (ON or OFF). However, because the

controller is actively scanning, unless the coil is disabled, the controller can also

alter the state of the coil. Coils are numbered from zero (coil 0001 = zero, coil

0002 = one, and so on). The data value 65,280 (FF00 HEX) will set the coil ON

and the value zero will turn it OFF; all other values are illegal and will not affect

that coil.
The use of Slave address 00 (Broadcast Mode) will force all attached Slaves to

modify the desired coil.

Note: Functions 5, 6, 15, and 16 are the only messages that will be recognized as valid for
broadcast.


The example below is a request to Slave number 11 to turn ON coil 0173.

Adr

Func

Data Coil # Hi

Data Coil # Lo

Data On/off Ind

Data

Error Check Field

11

05

00

AC

FF

00

CRC

Advertising