Configuring the MVI69-MCM Module

MVI69-MCM ♦ CompactLogix or MicroLogix Platform

User Manual

Modbus Communication Module

Page 64 of 167

ProSoft Technology, Inc.

March 22, 2011

Float Flag: "N" tells the Master to ignore the floating values and treat each

register data as a data point composed of 1 word, 2 bytes or 16 bits.
Float Start: Ignored.
DB Addr - same as when Float Flag: Y.
Reg Count - Tells the Master how many data points to send to the Slave.
Swap Code - same as when Float Flag: Y.
Func Code - same as when Float Flag: Y.
Addr in Dev - same as when Float Flag: Y as long as the Slave's Float Flag = Y.
In the above example, the Master's Modbus command to transmit inside the

Modbus packet will be as follows.

Slave
address

Function
Code

Address in
Device

Reg
Count

Byte
Count

Data

DEC

01

16

7100

2

4

85.37

HEX

01

10

1B BC

00 02

04

BD 71 42 AA

In this example, the Master's Modbus packet contains the data byte and data

word counts that have NOT been doubled from the amount specified by Reg

Count due to the Float Flag set to N. The Slave looks for the byte count in the

data packet to know the length of the data to read from the wire. Because of

insufficient byte count, some slaves will read only half the data from the Master's

transmission. Other slaves will read all 8 bytes in this example because they will

know where in the packet the data starts and ignore the byte count parameter

inside the Modbus packet.

Specific Example#3: Master is issuing Modbus command with FC 3 to transfer Float data
from Slave.

Float Flag: Not applicable with Modbus Function Code 3.
Float Start: Not applicable with Modbus Function Code 3.
DB Addr - Tells the Master where in its data memory to store the data obtained
from the Slave.
Reg Count - Tells the Master how many registers to request from the Slave.
Swap Code - same as above.