MVI69-MCM ♦ CompactLogix or MicroLogix Platform

Ladder Logic

Modbus Communication Module

User Manual

ProSoft Technology, Inc.

Page 77 of 167

March 22, 2011

Block Transfer Size = 120

Comm Format

Data - INT

Slot

The slot number in the rack where the module is installed

Input Assembly Instance

101

Input Size

122

Output Assembly Instance

100

Output Size

121

Configuration Assembly Instance 102
Configuration Size

0

Block Transfer Size = 240

Field

Recommended Value

Type

1769-MODULE Generic 1769 Module

Parent

Local

Name

MVI69

Description

MVI69 Application Module

Comm Format

Data - INT

Slot

The slot number in the rack where the module is installed

Input Assembly Instance

101

Input Size

242

Output Assembly Instance

100

Output Size

241

Configuration Assembly Instance 102
Configuration Size

0

5 Click N

EXT

to continue.

6 Select the

R

EQUEST

P

ACKET

I

NTERVAL

value for scanning the I/O on the

module. This value represents the minimum frequency the module will handle

scheduled events. This value should not be set to less than 1 millisecond.

Values between 1 and 10 milliseconds should work with most applications.