MVI69-MCM ♦ CompactLogix or MicroLogix Platform

Configuring the MVI69-MCM Module

Modbus Communication Module

User Manual

ProSoft Technology, Inc.

Page 21 of 167

March 22, 2011

2.1.2 Create the Module

1 Right-click

I/O

C

ONFIGURATION

and choose N

EW

M

ODULE

2 Select 1769-MODULE

3 Set the Module Properties values as follows:

Parameter

Value

Name

Enter a module identification string. Example: MVI69MCM

Description

Enter a description for the module. Example: ProSoft
communication module for Serial Modbus communications.

Comm Format

Select Data-INT

Slot

Enter the slot number in the rack where the MV69-MCM

module will be installed.

Input Assembly Instance

101

Input Size

62 / 122 / 242

Output Assembly Instance

100

Output Size

61 / 121 / 241

Configuration Assembly Instance

102

Configuration Size

0