ProSoft Technology MVI69-HART User Manual

Page 104

Advertising
background image

Reference

MVI69-HART ♦ CompactLogix Platform

User Manual

HART Multi-drop Master Communication Module

Page 104 of 169

ProSoft Technology, Inc.

March 29, 2012

Multi-drop Mode Example:
The intent is to show when using Multi-drop mode how the Auto-Poll DB Address

and Max Device Count parameters should be used.
If the configuration file sets the following parameters:

Parameter

Value

Config File Section

DB Address Status

3660


[HART PORT 0]

Auto-Poll DB Address

400

Max Device Count

15

DB Address Status

3661


[HART PORT 1]

Auto-Poll DB Address

1200

Max Device Count

15

The HART database has the following structure.

The configuration file for this example shows that when the MAX Device Address

parameter is configured as 15, the module will reserve 750 words for each

channel (15 devices x 50 words each) even though not all devices may be

present on the network.