ProSoft Technology MVI69-HART User Manual

Page 94

Advertising
background image

Reference

MVI69-HART ♦ CompactLogix Platform

User Manual

HART Multi-drop Master Communication Module

Page 94 of 169

ProSoft Technology, Inc.

March 29, 2012

Warm Boot (Block 9998)
This block is sent from the CompactLogix or MicroLogix processor to the module

(output image) when the module is required to perform a warm-boot (software

reset) operation. The following table describes the format of the control block.

Offset

Description

Length

0

9998

1

1 to n

Spare

n

n=60, 120, or 240 depending on the Block Transfer Size parameter (refer to the configuration file).

Cold Boot (Block 9999)
This block is sent from the CompactLogix processor to the module (output

image) when the module is required to perform the cold boot (hardware reset)

operation. This block is sent to the module when a hardware problem is detected

by the ladder logic that requires a hardware reset. The following table describes

the format of the control block.

Offset

Description

Length

0

9999

1

1 to n

Spare

n

n=60, 120, or 240 depending on the Block Transfer Size parameter (refer to the configuration file).

5.2.5 HART Channels

The MVI69-HART module supports the HART protocol as a Master on up to two

channels. Each channel is individually configurable.
The HART protocol uses the Bell 202 standard frequency shift-keying (FSK)

signal to communicate at 1200 baud, superimposed at a low level on the 4 to 20

mA analog measurement signal. Having an average value of zero, and FSK

signal causes no interference with the analog value. The HART devices are

powered from this 4 to 20 mA analog loop.
Both HART protocol channels in the module generate the Bell 202 FSK signal to

communicate in multi-drop mode with up to 15 HART devices and provide up to

250 mA supply for analog loop.

Advertising