MVI69-HART ♦ CompactLogix Platform

Ladder Logic

HART Multi-drop Master Communication Module

User Manual

ProSoft Technology, Inc.

Page 53 of 169

March 29, 2012

3.2

Adding the Module to an Existing CompactLogix Project

Important: The MVI69-HART module has a power supply distance rating of 2 (L43 and L45
installations on first 2 slots of 1769 bus, to the right of the processor).


If you are installing and configuring the module with a CompactLogix controller,

and you decide to use the standard sample ladder logic rather than importing the

Add-On Instruction (AOI) Rung, then follow these steps. If you are using a

MicroLogix controller, refer to the next section (page 57).
1 Add the MVI69-HART module to the project. Right-click the mouse button on

the I/O

C

ONFIGURATION

option in the Controller Organization window to

display a pop-up menu. Select the N

EW

M

ODULE

option from the

I/O

C

ONFIGURATION

menu.

This action opens the Select Module dialog box: