ProSoft Technology MVI69-HART User Manual

Page 61

Advertising
background image

MVI69-HART ♦ CompactLogix Platform

Diagnostics and Troubleshooting

HART Multi-drop Master Communication Module

User Manual

ProSoft Technology, Inc.

Page 61 of 169

March 29, 2012

The LEDs indicate the module’s operating status as follows:

LED

Color

Status

Indication

CFG

Green

On

NA

Off

NA

EP

Green

On

NA

Off

NA

Off

No data is being transferred on the Configuration/Debug port.

APP

Amber

Off

The MVI69-HART is working normally.

On

The MVI69-HART module program has recognized a

communication error.

BP

Amber

On

The LED is on when the module is performing a write

operation on the backplane.

Off

The LED is off when the module is performing a read
operation on the backplane. Under normal operation, the LED

should blink rapidly on and off.

OK

Red/
Green

Off

The card is not receiving any power and is not securely

plugged into the rack.

Green

The module is operating normally.

Red

The program has detected an error or is being configured. If
the LED remains red for over 10 seconds, the program has

probably halted. Remove the card from the rack and re-insert

the card to restart the module’s program.

BAT

Red

Off

The battery voltage is OK and functioning.

On

The battery voltage is low or battery is not present. Allow
battery to charge by keeping module plugged into rack for 24
hours. If BAT LED still does not go off, contact ProSoft

Technology, as this is not a user serviceable item.

CH01

Green

On

Data is being transmitted between the module and the

processor.

Off

CH02

Green

On

Data is being transmitted between the module and the

processor.

Off